Specifications

1. Specifications
Ceiling Mounted Cassette Type (Multi-flow)
Model
1 Cooling Capacity
2 Heating Capacity
Casing / Color
Dimensions: (H×W×D)
Rows × Stages × FPI
Coil (Cross
Fin Coil)
Face Area
Model
Type
Fan
Motor Output
Air Flow Rate (H/L)
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Liquid Pipes
Piping
Gas Pipes
Connections
Drain Pipe
Machine Weight (Mass)
4 Sound Level (H/L)
Safety Devices
Refrigerant Control
Connectable outdoor unit
Model
Color
Decoration
Dimensions: (H×W×D)
Panels
(Option)
Air Filter
Weight
Standard Accessories
Drawing No.
Notes:
270
FXFQ12MVJU
Btu/h
12,000
Btu/h
13,500
Galvanized Steel Plate
inch
9-1/8 × 33-1/8 × 33-1/8"
(mm)
(231.8 x 841.4 x 841.4 mm)
2 × 8 × 17
ft²
3.56
QTS45B14M
Turbo Fan
kW
0.04
cfm
460/350
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Foamed Polystyrene /
Foamed Polyethylene
inch
φ 1/4" (6.4 mm) (Flare Connection)
(mm)
inch
φ1/2 " (12.7 mm) (Flare Connection)
(mm)
VP25
inch
(
External Dia. 1-1/4
(mm)
Internal Dia. 1
Lbs
55 lbs (24.9 kg)
(kg)
dBA
31/28
Fuse, Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A Series
BYC125K-W1
White (10Y9/0.5)
inch
1-5/8 × 37-3/8 × 37-3/8"
(mm)
(41.2 x 949.3 x 949.3 mm)
Resin Net
(with Mold Resistant)
Lbs
11 lbs (5 kg)
(kg)
Operation manual, Installation manual,
Paper pattern for installation, Drain
hose, Clamp metal, Washers, Sealing
pads, Clamps, Screws, Insulation for
fitting.
1 Nominal cooling capacities are based on the following conditions:
Return air temperature: 80°FDB, 67°FWB
Outdoor temperature: 95°FDB
Equivalent ref. piping length: 25 ft (7.5 m) (Horizontal)
2 Nominal heating capacities are based on the following conditions:
Return air temperature: 70°FDB.
Outdoor temperature: 47°FDB, 43°FWB
Equivalent ref. piping length: 25 ft (7.5 m) (Horizontal)
3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of installation conditions.
FXFQ18MVJU
18,000
20,000
Galvanized Steel Plate
9-1/8 × 33-1/8 × 33-1/8"
(231.8 x 841.4 x 841.4 mm)
2 × 8 × 17
3.56
QTS45B14M
Turbo Fan
0.04
570/390
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Foamed Polystyrene /
Foamed Polyethylene
φ 1/4" (6.4 mm) (Flare Connection)
φ1/2 " (12.7 mm) (Flare Connection)
VP25
)
(
External Dia. 1-1/4
Internal Dia. 1
55 lbs (24.9 kg)
33/28
Fuse, Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A Series
BYC125K-W1
White (10Y9/0.5)
1-5/8 × 37-3/8 × 37-3/8"
(41.2 x 949.3 x 949.3 mm)
Resin Net
(with Mold Resistant)
11 lbs (5 kg)
Operation manual, Installation manual,
Paper pattern for installation, Drain
hose, Clamp metal, Washers, Sealing
pads, Clamps, Screws, Insulation for
fitting.
C:3D042686
SiUS34-801A_b
FXFQ24MVJU
24,000
27,000
Galvanized Steel Plate
9-1/8 × 33-1/8 × 33-1/8"
(231.8 x 841.4 x 841.4 mm)
2×8×17
3.56
QTS45B14M
Turbo Fan
0.04
670/490
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Foamed Polystyrene /
Foamed Polyethylene
φ3/8 " (9.5 mm) (Flare Connection)
φ5/8 " (15.8 mm) (Flare Connection)
VP25
)
(
External Dia. 1-1/4
Internal Dia. 1
55
34/29
Fuse, Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A Series
BYC125K-W1
White (10Y9/0.5)
1-5/8 × 37-3/8 × 37-3/8"
(41.2 x 949.3 x 949.3 mm)
Resin Net
(with Mold Resistant)
11
Operation manual, Installation manual,
Paper pattern for installation, Drain
hose, Clamp metal, Washers, Sealing
pads, Clamps, Screws, Insulation for
fitting.
)