12.Field Setting

12.1 Field Setting from Remote Controller

Individual function of indoor unit can be changed from the remote controller. At the time of
installation or after service inspection / repair, make the local setting in accordance with the
following description.
Incorrect settings may result in malfunction.
When an optional accessory is mounted on the indoor unit, the setting for the indoor unit may need
to be changed. Refer to information in the Option Handbook.
12.1.1 Wired Remote Controller <BRC1D71>
1. When in the normal mode, push the
2. During group control and you want to set by each individual indoor unit (when mode No. 20, 21,
3. Push the
4. Push the
5. Push the timer
6. Push the
(Example)
When setting the filter sign time to [Filter Dirtiness-High] in all group unit setting, set the Mode No.
to [10], Mode setting No. to [0] and setting position No. to [02].
Indoor Unit
enters the [FIELD SET MODE]. Select the desired [MODE NO.] with the
22, 23, 25 has been selected), push the time mode
No." to be set.
Note: This operation is not required when setting as a group.
button and select the first code No.
button and select the second code No.
button one time and "define" the currently set contents.
button to return to the normal mode.
button for 4 seconds or more, and operation then
button and select the "indoor unit
Field Setting
button.
299