E5" Outdoor Unit: Inverter Compressor Motor Lock - Daikin RTSQ20PY1 Service Manual

Vrv iii-c r-410a heat pump 50hz
Hide thumbs Also See for RTSQ20PY1:
Table of Contents

Advertisement

SiBE31-801_C
E5
4.17 "
" Outdoor Unit: Inverter Compressor Motor Lock
E5
Remote
Controller
Display
Applicable
RTSQ8P~16P (Outdoor Unit), BTSQ20P (Function Unit)
Models
Method of
Inverter PCB takes the position signal from UVW line connected between the inverter and
compressor, and the malfunction is detected when any abnormality is observed in the phase-
Malfunction
current waveform.
Detection
Malfunction
This malfunction will be output when the inverter compressor motor does not start up even in
forced startup mode.
Decision
Conditions
Supposed
Causes
Troubleshooting
Inverter compressor lock
High differential pressure (0.5MPa or more)
Incorrect UVW wiring
Faulty inverter PCB
Stop valve is left in closed.
Troubleshooting by Indication on the Remote Controller
248