Field Setting
Setting item 0 displays the contents of various settings
EMG operation /
backup operation
setting
Defrost select setting
Te setting
Tc setting
expressing are as follows:
254
ON
OFF
Short
Medium
Long
L
M
H N~R
L
M
H
Data such as addresses and number of unitsare expressed as binary numbers; the two ways of
9 797997
16
4
1
32
8
2
977 7979
64
16
No.12
128 32
977 7997
4
1
No.13
8
2
See the preceding page for a list of data, for No. 0 - 25.
9 7 7 8 7 7 7
9 7 7 7 7 7 7
9 7 7 7 8 7 7
9 7 7 7 9 7 7
9 7 7 7 7 7 7
9 7 7 7 7 7 7
9 7 7 7 7 9 7
9 7 7 7 7 8 7
9 7 7 7 7 7 7
9 7 7 7 7 7 9
9 7 7 7 7 7 8
The No. 1 cool/heat unified address is expressed as a binary
number consisting of the lower 6 digits. (0 - 63)
In
the address is 010110 (binary number), which translates to
16 + 4 + 2 = 22 (base 10 number). In other words, the address
is 22.
The number of terminal blocks for No. 12 and 13 is expressed
as an 8-digit binary number, which is the combination of four
upper, and four lower digits for No. 12 and 13 respectively. (0 -
128)
In
the address for No. 12 is 0101, the address for No. 13 is
0110, and the combination of the two is 01010110 (binary
number), which translates to 64 + 16 + 4 + 2 = 86 (base 10
number). In other words, the number of terminal block is 86.