SiUS34-801A_b
Detailed Setting Procedure of Low Noise Operation and Demand Control
1. Setting mode 1 (H1P off)
2. Setting mode 2 (H1P on)
Setting
Setting
Setting No. indication
No.
contents
H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P
External low
12
noise /
Demand
setting
22
Night-time
low noise
setting
25
External low
noise
setting
26
Night-time
low noise
start setting
27
Night-time
low noise
end setting
29
Capacity
precedence
setting
30
Demand
setting 1
Normal
32
demand
setting
Setting mode indication section
VRVIII R-410A Heat Pump 60Hz
In setting mode 2, push the BS1 (MODE button) one time. → Setting mode 2 is entered and
H1P lights.
During the setting mode 1 is displayed, "In low noise operation" and "In demand control" are
displayed.
In setting 1, push and hold the BS1 (MODE button) for more than 5 seconds. → Setting mode 2
is entered and H1P lights.
Push the BS2 (SET button) several times and match the LED display with the Setting No. you
want.
Push the BS3 (RETURN button) one time, and the present setting content is displayed.
→ Push the BS2 (SET button) several times and match the LED display with the setting content
(as shown below) you want.
Push the BS3 (RETURN button) two times. → Returns to
Push the BS1 (MODE button) one time. → Returns to the setting mode 1 and turns H1P off.
Setting No. indication
Setting No. indication section
.
: ON
Setting
Setting contents indication (Initial setting)
contents
H1P H2P H3P H4P H5P H6P H7P
NO (Factory
setting)
YES
OFF
(Factory
setting)
Mode 1
Mode 2
Mode 3
Mode 1
Mode 2
(Factory
setting)
Mode 3
PM 8:00
PM 10:00
(Factory
setting)
PM 0:00
AM 6:00
AM 7:00
AM 8:00
(Factory
setting)
Low noise
precedence
(Factory
setting)
Capacity
precedence
60 % of
rated power
consumption
70 % of
rated power
consumption
(Factory
setting)
80 % of
rated power
consumption
OFF
(Factory
setting)
ON
Set contents indication section
Field Settings
: OFF
: Blink
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
111