Field Settings
•
•
O Emergency operation by setting outdoor unit PC board
114
Automatically disable the defective outdoor unit from operating, and then operate other outdoor
units.
The following section shows malfunction codes on which this emergency operation is possible.
E3, E4, E5
F3
H9
J2, J3, J5, J6, J7, J9, JA, JC
L3, L4, L5, L8, L9, LC
U2, UJ
In malfunction stop state of the outdoor unit due to defective compressor, by setting the relevant
compressor or relevant outdoor unit to Disabling operation setting, the emergency operation
is conducted with operational compressors or outdoor units.
SiUS34-801A_b
VRVIII R-410A Heat Pump 60Hz