Daikin RXYQ96PYDN Service Manual page 295

R-410a heat pump 60hz, r-410a heat recovery 60hz
Hide thumbs Also See for RXYQ96PYDN:
Table of Contents

Advertisement

Specifications
Wall Mounted Type
Model
1 Cooling Capacity
2 Heating Capacity
Casing Color
Dimensions: (H×W×D)
Rows × Stages × FPI
Coil (Cross
Fin Coil)
Face Area
Model
Type
Fan
Motor Output
Air Flow Rate (H/L)
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Liquid Pipes
Gas Pipes
Piping
Connections
Drain Pipe
Machine Weight (Mass)
4 Sound Level (H)
Safety Devices
Refrigerant Control
Connectable outdoor unit
Standard Accessories
Drawing No.
Notes:
280
FXAQ07MVJU
Btu/h
7,500
Btu/h
8,500
White (3.0Y8.5/0.5)
11–3/8 × 31–1/4 ×9"
in (mm)
(289 x 794 x 229 mm)
2×14×17
ft²
1.73
QCL9661M
Cross Flow Fan
kW
0.04
cfm
260/160
Direct Drive
Microprocessor Thermostat for Cooling
and Heating
Foamed Polystyrene /
Foamed Polyethylene
Resin Net (Washable)
φ 1/4" (6.4 mm) (Flare Connection)
in (mm)
φ1/2 " (12.7 mm) (Flare Connection)
in (mm)
VP13
in (mm)
External Dia. 11/16" (17.5 mm)
Internal Dia. 1/2" (12.7 mm)
Lbs (kg)
25 lbs (11.3 kg)
dBA
Fuse
Electronic Expansion Valve
R-410A Series
Operation Manual, Installation Manual,
Installation Panel, Paper Pattern for
Installation, Insulation Tube, Clamps,
Screws.
1 Nominal cooling capacities are based on the following conditions:
Return air temperature: 80°FDB, 67°FWB
Outdoor temperature: 95°FDB
Equivalent ref. piping length: 25 ft (7.5 m) (Horizontal)
2 Nominal heating capacities are based on the following conditions:
Return air temperature: 70°FDB.
Outdoor temperature: 47°FDB, 43°FWB
Equivalent ref. piping length: 25ft (Horizontal)
3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of installation conditions.
FXAQ09MVJU
White (3.0Y8.5/0.5)
11–3/8 × 31–1/4 ×9"
(289 x 794 x 229 mm)
Cross Flow Fan
Microprocessor Thermostat for Cooling
Foamed Polystyrene /
Foamed Polyethylene
Resin Net (Washable)
φ 1/4" (6.4 mm) (Flare Connection)
φ1/2 " (12.7 mm) (Flare Connection)
External Dia. 11/16" (17.5 mm)
Internal Dia. 1/2" (12.7 mm)
25 lbs (11.3 kg)
36
Electronic Expansion Valve
R-410A Series
Operation Manual, Installation Manual,
Installation Panel, Paper Pattern for
Installation, Insulation Tube, Clamps,
Screws.
C:3D046038A
9,500
10,500
2×14×17
1.73
QCL9661M
0.04
280/175
Direct Drive
Microprocessor Thermostat for Cooling
and Heating
φ 1/4" (6.4 mm) (Flare Connection)
φ1/2 " (12.7 mm) (Flare Connection)
VP13
External Dia. 11/16" (17.5 mm)
Internal Dia. 1/2" (12.7 mm)
37
Fuse
Electronic Expansion Valve
Operation Manual, Installation Manual,
Installation Panel, Paper Pattern for
Installation, Insulation Tube, Clamps,
Screws.
SiUS34-801A_b
FXAQ12MVJU
12,000
13,500
White (3.0Y8.5/0.5)
11–3/8 × 31–1/4 ×9"
(289 x 794 x 229 mm)
2×14×17
1.73
QCL9661M
Cross Flow Fan
0.04
300/180
Direct Drive
and Heating
Foamed Polystyrene /
Foamed Polyethylene
Resin Net (Washable)
VP13
25 lbs (11.3 kg)
38
Fuse
R-410A Series
Indoor Unit

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents