Daikin RXYQ96PYDN Service Manual page 536

R-410a heat pump 60hz, r-410a heat recovery 60hz
Hide thumbs Also See for RXYQ96PYDN:
Table of Contents

Advertisement

SiUS34-801A_b
(3) If the piping length between the outside units exceeds 80 inches, create a rise of 80 inches, or
Appendix
Prohibited pattern
Front connections
Side (bottom) connections
Oil remains in the unit A when system stops.
Change as shown in the figure below.
Connect straightly
more in the gas piping under a length of 80 inches, from the outside unit multi connection piping
kit.
If less than 80 in.
If 80 in. or more
Unit A
to indoor unit
Unit A
to indoor unit
Oil remains in the stopping outside unit.
Change to pattern 1 or pattern 2
Unit
Unit
B
A
Unit
A
Oil remains in the unit B when system stops.
Change as shown in the figure below.
Connect straightly
Unit
Unit
B
A
Unit
A
Gas pipe between
outside units
to indoor unit
Gas pipe between
outside units
to indoor unit
Piping Installation Point
Unit B
Unit B
Unit
A
Unit
Unit
B
B
Put rising
Unit
A
Unit
Unit
B
B
Rising height :
8 in. or more
Unit
Unit
A
B
less than 80 in.
Rising height :
Unit
Unit
8 in. or more
A
B
less than 80 in.
521