Special Control
7.5.1 Pump-down Residual Operation in Cooling Operation
If the liquid refrigerant stays in the Evaporator at the startup of a compressor, this liquid refrigerant enters the compressor,
thus resulting in diluted oil in the compressor and then degraded lubrication performance.
Consequently, in order to recover the refrigerant in the Evaporator while the compressor stops, the pump-down residual
operation is conducted.
Actuator
Compressor 1
Compressor 2
Outdoor unit fan 1
Outdoor unit fan 2
Electronic expansion valve (Main)
Electronic expansion valve
(Subcooling)
Electronic expansion valve
(Refrigerant charge)
Four-way valve (Heat exchanger
switch)
Four-way valve (High/low
pressure gas pipe switch)
Solenoid valve (Main bypass)
Solenoid valve (Hot gas)
Solenoid valve (Refrigerant
regulator liquid pipe)
Solenoid valve (Refrigerant
regulator gas vent pipe)
Solenoid valve (Refrigerant
regulator exhaust pipe)
Solenoid valve (Refrigerant
regulator discharge pipe)
Ending conditions
* Pe_min and Pc_max indicate the minimum and maximum values in the system, respectively.
206
Elect.
symbol
Symbol
REYQ
REMQ
M1C M1C
124 Hz+OFF
M2C M2C
M1F
M1F
Fan control
M2F
M2F
Y1E
EVM
Y1E 1375 pls
Y3E
Y2E
EVT
Y3E 0 pls
Y5E
EVJ
Y4E
Y2E 80 pls
Y2S
20SA
Y3S OFF
Y9S
20SB
Y8S
Y2S ON
Y5S
SVE
Y10S Y6S ON
SVP
Y4S
Y5S OFF
SVL
Y3S
Y4S OFF
SVG
Y1S
Y1S OFF
SVO
Y7S
Y7S OFF
SVT
Y6S
Y8S OFF
or
Master unit operation
• 5 min.
• Pe_min<71.05psi ∗
• Pc_max<426.3psi ∗
• Master unit Tdi>230°F
• Master unit Tp>257°F
VRVIII R-410A Heat Recovery 60Hz
SiUS34-801A_b
Slave unit operation
OFF
Fan control
1375 pls
0 pls
80 pls
OFF
ON
ON
OFF
OFF
OFF
OFF
OFF