Protection Control
8.5
STD Compressor Overload Protection
This control is used to prevent abnormal heating due to overcurrent to the compressor resulting
from failures of the STD compressor, such as locking.
STD compressor ON
Demand to operate.
STD compressor OFF for 30 min.*
When occurring 3 times within 90 min.,
the malfunction code [E6] is displayed.
70
CT detection current value>15.0A
34 (230V)
*If the power supply is reset while in
operation prohibition mode, the prohibition
timer will continue counting when the
(460)
power supply is turned ON.
SiUS34-801A_b
VRVIII R-410A Heat Pump 60Hz