Std Compressor Overload Protection - Daikin RXYQ96PYDN Service Manual

R-410a heat pump 60hz, r-410a heat recovery 60hz
Hide thumbs Also See for RXYQ96PYDN:
Table of Contents

Advertisement

Protection Control
8.5

STD Compressor Overload Protection

This control is used to prevent abnormal heating due to overcurrent to the compressor resulting
from failures of the STD compressor, such as locking.
STD compressor ON
Demand to operate.
STD compressor OFF for 30 min.*
When occurring 3 times within 90 min.,
the malfunction code [E6] is displayed.
70
CT detection current value>15.0A
34 (230V)
*If the power supply is reset while in
operation prohibition mode, the prohibition
timer will continue counting when the
(460)
power supply is turned ON.
SiUS34-801A_b
VRVIII R-410A Heat Pump 60Hz