Daikin RXYQ96PYDN Service Manual page 263

R-410a heat pump 60hz, r-410a heat recovery 60hz
Hide thumbs Also See for RXYQ96PYDN:
Table of Contents

Advertisement

Field Setting
a. Setting mode 1
This mode is used to set and check the following items:
(1) Current operating conditions (Normal / Abnormal / In check operation)
(2) Low noise operating conditions (In normal operation / In low noise operation)
(3) Demand operating conditions (In normal operation / In demand operation)
Procedure for checking check items
The system is normally set to "Setting
mode 1".
Should the system be set to any
mode other than that, push the
MODE (BS1) button to set the
system to "Setting mode 1".
Check the system for each condition
through LED displays. (Refer to
information in table on the right.)
Pushing the RETURN (BS3) button
will bring the system to the initial
state of "Setting mode 1".
Press BS1 (MODE button) for more than 5 sec.
Setting mode 2
Setting item selection
(SET button)
Setting condition
selection (SET button)
Setting condition
(Contents) display
248
MODE
TEST
H1P
H2P
7
7
(V2763)
Press BS3
(RETURN button).
Press BS3
(RETURN button).
Press BS3
(RETURN button).
Press BS1
(MODE button).
COOL/HEAT select
Low
IND
MASTER
SLAVE
noise
H3P
H4P
H5P
H6P
8
7
7
7
(Set): Select mode with BS2 (SET button) in each selection step.
Setting mode 1
Press BS1(MODE button).
(Initial condition)
Demand
H7P
7
Current operating conditions
7Normal 8Abnormal
9In preparation or in
check operation
Low noise operating conditions
7In normal operation
8In low noise operation
Demand operating conditions
7In normal operation
8In demand operation
Monitor mode
Check item selection
(SET button)
Press BS3
(RETURN button).
Contents display
Press BS3
(RETURN button).
Press BS1
(MODE button).
VRVIII R-410A Heat Recovery 60Hz
SiUS34-801A_b
(V2762)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents