(13) Air Flow Direction Setting
Set the
blocking pad has been installed.) The second code No. is factory set to [01].
Setting Table
(14) Setting of Air Flow Direction Adjustment Range
Make the following
Setting Table
∗ Some indoor unit models are not equipped with draft prevention (upward) function.
(15) Setting of the Static Pressure Selection (for FXDQ model)
Indoor Unit
In the Case of FXFQ12~30
First
Second
Mode
code
code
No.
No.
No.
Standard (N)
01
High Ceiling (H)
0
02
Higher Ceiling (S)
03
In the Case of FXFQ36
First
Second
Mode
code
code
No.
No.
No.
Standard (N)
01
0
02
High Ceiling (H)
03
Higher Ceiling (S)
airflow
direction of indoor units as given in the following table . (Set when optional air outlet
Mode No.
First Code No.
13 (23)
1
airflow
Mode No.
13 (23)
Model No.
13 (23)
Setting
4-way Outlets
Lower than
9 ft
Lower than
10 ft
Lower than
12 ft
Setting
4-way Outlets
Lower than
12 ft
Lower than 12 ft
Lower than 14 ft
Second Code
No.
01
F : 4-direction airflow
02
T : 3-direction airflow
03
W : 2-direction airflow
direction setting according to the respective purpose.
First Code No.
4
First Code No.
5
Ceiling height
3-way Outlets
Lower than
10 ft
Lower than
11 ft
Lower than
12 ft
Ceiling height
3-way Outlets
Lower than 12 ft
Lower than 13 ft
Lower than 14 ft
Setting
Second Code No.
01
02
Downward (Ceiling
03
soiling prevention)
Second Code No.
External static pressure
01
Standard (0.06"Wg)
High static pressure
02
Field Setting
2-way Outlets
Lower than
12 ft
Lower than
13 ft
2-way Outlets
Lower than 14 ft
Lower than 14 ft
Setting
Upward (Draft
prevention)
Standard
(0.17"Wg)
307