Daikin RXYQ96PYDN Service Manual page 72

R-410a heat pump 60hz, r-410a heat recovery 60hz
Hide thumbs Also See for RXYQ96PYDN:
Table of Contents

Advertisement

SiUS34-801A_b
Solenoid valve (discharge pipe
of refrigerant regulator)
Ending conditions
7.4.2 Multi Outdoor Unit System
[Start conditions]
Referring to the following conditions, start defrost operation.
• When there is a decrease in the coefficient of heat transfer of outdoor unit heat exchanger
• When there is a drop in the temperature of outdoor unit heat exchanger outlet (Tb)
&
• When the low pressure stays low for a certain amount of time (2 hours minimum)
Furthermore, the thermal conductivity of outdoor unit heat exchanger is calculated by Tc, Te, and compressor loads.
Defrosting outdoor unit actuator
Compressor 1
Compressor 2
Outdoor unit fan 1
Four way valve (for heat
exchanger selection)
Four way valve (for high- and low-
pressure gas pipe selection)
Electronic expansion valve (main) EVM
Electronic expansion valve
(subcooling)
Electronic expansion valve
(refilling refrigerant)
Solenoid valve (main bypass)
Solenoid valve (hot gas)
Solenoid valve (liquid pipe of
refrigerant regulator)
Solenoid valve (gas discharge
pipe of refrigerant regulator)
Solenoid valve (drain pipe of
refrigerant regulator)
Solenoid valve (discharge pipe of
refrigerant regulator)
End conditions
VRVIII R-410A Heat Pump 60Hz
SVT
Y6S
Elect. symbol
For any model
Symbol
other than
144PTJU
M1C
210Hz+ON
M2C
Pcmax>355.25psi
M1F
Pcmax>440.8psi
20SA
Y3S
OFF
20SB
Y2S
Holds
Y1E
1375pls
EVT
Y3E
SH control
EVJ
Y2E
80pls
SVE
Y6S
ON
SVP
Y5S
OFF
SVL
Y4S
0pls
SVG
Y1S
0pls
SVO
Y7S
0pls
SVT
Y8S
0pls
RXYQ72~120P (by unit)
or
Y8S
0pls
• 10 min.
• Tb>51.8°F
or
continues for a
period of consecutive
90 sec.
Defrost operation
OFF
Pcmax<342.2psi
FANSTEP4
Pcmax<427.75psi
FANSTEP6
• 5 min. and 30 sec.
• Tb > 51.8°F for a period
of 10 consecutive sec.
• Pc_max > 440.8psi
Special Control
0pls
• 160 sec.
• Pc-Pe>58psi
or
continues for a period
of consecutive
120 sec.
Operation after defrost
210Hz+ON
OFF
Pcmax>355.25psi
Pcmax<342.2psi
FANSTEP4
Pcmax>440.8psi
Pcmax<427.75psi
FANSTEP6
OFF
Holds
0pls
0pls
80pls
OFF
OFF
0pls
0pls
0pls
0pls
• 30 sec.
or
• Pc_max>440.8psi
57