Field Settings
Pushbutton switches
There are the following three setting modes.
Initial status (when normal) : Used to select the cool/heat setting. Also on during abnormal, low
noise control, and demand control.
Used to modify the operating status and to set program addresses, etc. Usually used in servicing
the system.
Used to check the program made in
98
Single-outdoor-unit
7
system
7
Outdoor-
Master
multi
Slave 1
7
system
MODE
BS1
Used to change
the setting mode
Setting mode 1 (H1P off)
Setting mode 2 (H1P on)
Monitor mode (H1P blinks)
Mode changing procedure 1
Using the MODE button, the modes can be changed as follows.
Push and hold the BS1
(MODE button) for 5 seconds.
Setting mode 2
Push the BS1(MODE button) one time.
MODE
On
H1P
7
8
7
7
8
7
7
7
7
SET
RETURN
TEST
REWIRING
BS2
BS3
BS4
BS5
Used for
Used to set up address
onsite setting
when wiring is changed
or an indoor unit is added
Used for check operation and
test operation
[Setting mode 2]
.
(Normal)
Setting mode 1
MODE
Off
H1P
SiUS34-801A_b
7
7
7
7
7
7
7
7
7
Push the BS1(MODE button)
one time.
Monitor mode
MODE
H1P
VRVIII R-410A Heat Pump 60Hz
7
8
9
Blinking
(V2761)