E6" Outdoor Unit: Std Compressor Motor Overcurrent/Lock - Daikin VRV II RXYQ8MY1K Service Manual

R-410a heat pump 50/60hz for high outdoor temperature use
Table of Contents

Advertisement

Troubleshooting by Indication on the Remote Controller
3.17 " E6 " Outdoor Unit:
Lock
E6
Remote
Controller
Display
Applicable
RXYQ8~30MY1K (E), YLK (E)
Models
Method of
Detects the overcurrent with current sensor (CT).
Malfunction
Detection
Malfunction
Malfunction is decided when the detected current value exceeds the below mentioned value for
2 seconds.
Decision
Conditions
Supposed
Causes
170
STD Compressor Motor Overcurrent/
400 V unit : 15.0 A
Closed stop value
Obstacles at the discharge port
Improper power voltage
Faulty magnetic switch
Faulty compressor
Faulty current sensor