12.1.4 Cool / Heat Mode Switching
Set Cool/Heat Separately for Each BS Unit by Cool/Heat Selector.
Set remote controller change over switch (SS1, SS2) as following:
• When using COOL/HEAT selector, turn this switch to the BS side.
When using cool/heat selector, connect to the terminal A, B and C on the terminal block of the
electric parts box.
EXAMPLE OF TRANSMISSION LINE CONNECTION
• Example of connecting transmission wiring.
Outside unit
TO IN/D UNIT TO OUT/D UNIT
F1 F2
F1 F2
A
B
F1
F2
F1
F2
IN/D
OUT/D.BS
C
BS unit A
F1
F2
F2
F1
VRVIII R-410A Heat Recovery 60Hz
1
1
2
2
SS1
SS2
Connect the transmission wirings as shown in the Fig. 1.
If the indoor unit is connected as the cool-only unit, it is wired to the
terminal of
F1
F2
OUT/D.BS
F1
F2
F1
F2
IN/D
OUT/D.BS
Final BS unit
To the indoor unit where
the selection of heating
and cooling is available.
Branch wiring
Use 2-core wires.
(There is no polarity.)
F1
F2
F1
F2
IN/D
OUT/D.BS
BS unit B
F1
F2
COOL/HEAT
selector
NOTE:
This setting must be completed
before turning power supply ON.
the last BS unit.
F1 F2
1st unit
Cooling only
Cool/heat selector remote
control wiring
Use 3-core wires.
(Keep in mind the polarity.)
A
B
F1
IN/D
C
Final BS unit
COOL/HEAT
selector
Fig. 1
F1 F2
Final unit
A
B
F2
F1
F2
OUT/D.BS
C
F1
F2
COOL/HEAT
selector
Indoor unit for cooling
Field Setting
F1
F2
F1
F2
255