Field Setting
12.1.6 Detailed Explanation of Setting Modes
(1) Filter Sign Setting
If switching the filter sign ON time, set as given in the table below.
Set Time
Setting
Contamination Light
Contamination Heavy
(2) Ultra-Long-Life Filter Sign Setting
When a Ultra-long-life filter is installed, the filter sign timer setting must be changed.
Setting Table
(3) Selection of Thermistor
Select the thermistor to control room temperature.
The factory setting for the Second Code No. is [01] and room temperature is controlled by the
indoor unit suction air thermistor and remote controller thermistor.
When the Second Code No. is set to [02], room temperature is controlled by the suction air
thermistor.
When the Second Code No. is set to [03], room temperature is controlled by the remote controller
thermistor.
(4) [Filter Cleaning] Displayed or Not Displayed
Whether or not to display [Filter Cleaning] after operation of certain duration can be selected.
304
Filter Specs.
Mode No.
Setting Switch No.
10 (20)
Mode No.
First Code No.
10 (20)
2
Mode No.
10 (20)
Standard
200 hrs.
100 hrs.
Setting Position No.
1
Second Code No. Thermistor that controls room temperature
01
02
03
First Code No.
Second Code No.
3
Long Life
Ultra Long Life Filter
2,500 hrs.
1,250 hrs.
01
Long-Life Filter
02
Ultra-Long-Life Filter (1)
03
Indoor air thermistor for remote controller and
suction air thermistor for indoor unit
Suction air thermistor for indoor unit
Thermistor for remote controller
"Filter Cleaning" display
01
02
SiUS34-801A_b
10,000 hrs.
5,000 hrs.
Setting
Display
No display
Indoor Unit