SiUS34-801A_b
MC
4.4
Address Duplication, Improper Setting
MC
Remote
Controller
Display
Applicable
Central remote controller
Models
Schedule timer
Method of
Malfunction
Detection
DIII-NET
transmission
data
Malfunction
Decision
Conditions
Supposed
Causes
Troubleshooting
Two or more units of central remote controllers and Intelligent Touch Controllers are connected,
and all of them are set to master unit central setting or slave unit central setting.
Two units of schedule timers are connected.
Address duplication of centralized controller
Troubleshooting (OP: Central Remote Controller)
Intelligent Touch Controller
451