Daikin RXYQ96PYDN Service Manual page 298

R-410a heat pump 60hz, r-410a heat recovery 60hz
Hide thumbs Also See for RXYQ96PYDN:
Table of Contents

Advertisement

SiUS34-801A_b
Concealed Floor Standing Type
Model
1 Cooling Capacity
2 Heating Capacity
Casing Color
Dimensions: (H×W×D)
Rows × Stages × FPI
Coil (Cross
Fin Coil)
Face Area
Model
Type
Fan
Motor Output
Air Flow Rate (H/L)
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Liquid Pipes
Piping
Gas Pipes
Connections
Drain Pipe
Machine Weight (Mass)
4 Sound Level (H/L)
Safety Devices
Refrigerant Control
Connectable Outdoor Unit
Standard Accessories
Drawing No.
Notes:
Indoor Unit
FXNQ12MVJU
Btu/h
12,000
Btu/h
13,500
Galvanized Steel Plate
24 × 42–1/8 ×8–5/8"
in (mm)
(609.6 x 1070 x 219.1 mm)
3×14×17
ft²
2.15
2D14B13
Sirocco Fan
kW
0.03
cfm
280/210
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber/ Urethane Foam
Resin Net (with Mold Resistant)
φ1/4 " (6.4 mm) (Flare Connection)
in (mm)
φ1/2 " (12.7 mm) (Flare Connection)
in (mm)
φ27/32 O.D (Vinyl Chloride)
in (mm)
(21.43 mm)
Lbs(kg)
66 lbs (29.9 kg)
dBA
36
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A Series
Operation Manual, Installation
Manual, Insulation for Fitting, Drain
Hose, Clamps, Screws, Washers, Level
Adjustment Screw.
1 Nominal cooling capacities are based on the following conditions:
Return air temperature: 80°FDB, 67°FWB
Outdoor temperature: 95°FDB
Equivalent ref. piping length: 25 ft (7.5 m) (Horizontal)
2 Nominal heating capacities are based on the following conditions:
Return air temperature: 70°FDB.
Outdoor temperature: 47°FDB, 43°FWB
Equivalent ref. piping length: 25 ft (7.5 m) (Horizontal)
3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of installation conditions.
FXNQ18MVJU
18,000
20,000
Galvanized Steel Plate
24 × 53-1/8 ×8–5/8"
(609.6 x 1349 x 219.1 mm)
3×14×17
3.04
2D14B20
Sirocco Fan
0.04
490/380
Direct Drive
Microprocessor Thermostat for Cooling
and Heating
Glass Fiber/ Urethane Foam
Resin Net (with Mold Resistant)
φ1/4 " (6.4 mm) (Flare Connection)
φ1/2 " (12.7 mm) (Flare Connection)
φ27/32 O.D (Vinyl Chloride)
(21.43 mm)
80 lbs (26.3 kg)
40
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A Series
Operation Manual, Installation Manual,
Insulation for Fitting, Drain Hose,
Clamps, Screws, Washers, Level
Adjustment Screw.
3D045640
Specifications
FXNQ24MVJU
24,000
27,000
Galvanized Steel Plate
24 × 53-1/8 ×8–5/8"
(609.6 x 1349 x 219.1 mm)
3×14×17
3.04
2D14B20
Sirocco Fan
0.04
560/420
Direct Drive
Microprocessor Thermostat for Cooling
and Heating
Glass Fiber/ Urethane Foam
Resin Net (with Mold Resistant)
φ3/8 " (9.5 mm) (Flare Connection)
φ5/8 " (15.8 mm) (Flare Connection)
φ27/32 O.D (Vinyl Chloride)
(21.43 mm)
80 lbs (26.3 kg)
41
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A Series
Operation Manual, Installation Manual,
Insulation for Fitting, Drain Hose,
Clamps, Screws, Washers, Level
Adjustment Screw.
283