Field Setting
(16) Humidification When Heating Thermostat is OFF
Setting to Humidification Setting turns ON the humidifier if suction temperature is 20ºC or above
and turns OFF the humidifier if suction temperature is 18ºC or below when the heating thermostat is
OFF.
(17) Setting of Direct Duct Connection
Used when fresh air intake kit equipped with fan is connected. The indoor fan carries out
residual operation for one minute after the thermostat is stopped to prevent air filter dust from
scattering.
(18) Interlocked Operation between Humidifier and Drain Pump
Used to interlock the humidifier with the drain pump. When water is drained out of the unit, this
setting is unnecessary.
(19) Individual Setting of Ventilation
Set to perform individual operation of heat-reclaim ventilation using the remote controller/central
unit if the option is available.
308
Mode No.
First Code No.
15 (25)
Mode No.
First Code No.
15 (25)
Mode No.
First Code No.
15 (25)
Mode No.
First Code No.
15 (25)
Second Code No.
01
1
02
Second Code No.
01
2
02
Second Code No.
01
3
02
Second Code No.
01
5
02
SiUS34-801A_b
Setting
Setting of humidifier
Contents
Without direct duct
connection
With direct duct
connection equipped
with fan
Contents
Individual operation of
humidifier
Interlocked operation
between humidifier and
drain pump
Contents
Individual operation of
ventilation
Indoor Unit