Daikin VRV III Technical Data Manual

Daikin VRV III Technical Data Manual

Heat recovery, with connection to heating only hydrobox
Hide thumbs Also See for VRV III:

Advertisement

Air Conditioners

Technical Data

VRV®III heat recovery, with connection to heating only hydrobox
E E D E N 1 1 - 2 0 0
REYAQ-P

Advertisement

Table of Contents
loading

Summary of Contents for Daikin VRV III

  • Page 1: Technical Data

    Air Conditioners Technical Data VRV®III heat recovery, with connection to heating only hydrobox E E D E N 1 1 - 2 0 0 REYAQ-P...
  • Page 2 Air Conditioners Technical Data VRV®III heat recovery, with connection to heating only hydrobox E E D E N 1 1 - 2 0 0 REYAQ-P...
  • Page 3: Table Of Contents

    ® • Outdoor Unit • VRV III heat recovery, with connection to heating only hydrobox • REYAQ-P TABLE OF CONTENTS REYAQ-P Specifications ............2 Technical Specifications .
  • Page 4: Specifications

    3.51 3.19 4.27 4.24 4.09 3.91 Maximum number of connectable indoor units Indoor index Min. connection Nom. Max. Casing Colour Daikin White Material Painted galvanized steel plate Dimensions Unit Height 1,680 Width 1,300 Depth Packed unit Height 1,885 Width 1,425...
  • Page 5 ® • Outdoor Unit • VRV III heat recovery, with connection to heating only hydrobox • REYAQ-P Specifications 1-1 Technical Specifications REYAQ10P REYAQ12P REYAQ14P REYAQ16P Piping Liquid Type Braze connection connections 9.52 12.7 Type Braze connection 22.2 28.6 Discharge Type Braze connection 19.1 22.2...
  • Page 6: Electrical Specifications

    ® • Outdoor Unit • VRV III heat recovery, with connection to heating only hydrobox • REYAQ-P Specifications 1-2 Electrical Specifications REYAQ10P REYAQ12P REYAQ14P REYAQ16P Power supply Phase Frequency Voltage 380-415 Voltage range Min. Max. Current Zmax Text 0.27 Current - 50Hz Maximum running current 22.1 22.3 32.8...
  • Page 7: Options

    ® • Outdoor Unit • VRV III heat recovery, with connection to heating only hydrobox • REYAQ-P Options 2 - 1 Options ® • VRV Systems • Outdoor Unit...
  • Page 8: Selection Procedure

    ® • Outdoor Unit • VRV III heat recovery, with connection to heating only hydrobox • REYAQ-P Selection procedure 3 - 1 Selection Procedure ® • VRV Systems • Outdoor Unit...
  • Page 9: Capacity Tables

    ® • Outdoor Unit • VRV III heat recovery, with connection to heating only hydrobox • REYAQ-P Capacity tables 4 - 1 Cooling Capacity Tables REYAQ10P TC: Total Capacity: kW ; PI: Power Input: kW (compressor + outdoor fan motor) Indoor air temperature: 14.0 °CWB 16.0 °CWB...
  • Page 10 ® • Outdoor Unit • VRV III heat recovery, with connection to heating only hydrobox • REYAQ-P Capacity tables 4 - 1 Cooling Capacity Tables REYAQ10P TC: Total Capacity: kW ; PI: Power Input: kW (compressor + outdoor fan motor) Indoor air temperature: 14.0 °CWB 16.0 °CWB...
  • Page 11 ® • Outdoor Unit • VRV III heat recovery, with connection to heating only hydrobox • REYAQ-P Capacity tables 4 - 1 Cooling Capacity Tables REYAQ12P TC: Total Capacity: kW ; PI: Power Input: kW (compressor + outdoor fan motor) Indoor air temperature: 14.0 °CWB 16.0 °CWB...
  • Page 12 ® • Outdoor Unit • VRV III heat recovery, with connection to heating only hydrobox • REYAQ-P Capacity tables 4 - 1 Cooling Capacity Tables REYAQ12P TC: Total Capacity: kW ; PI: Power Input: kW (compressor + outdoor fan motor) Indoor air temperature: 14.0 °CWB 16.0 °CWB...
  • Page 13 ® • Outdoor Unit • VRV III heat recovery, with connection to heating only hydrobox • REYAQ-P Capacity tables 4 - 1 Cooling Capacity Tables REYAQ14P TC: Total Capacity: kW ; PI: Power Input: kW (compressor + outdoor fan motor) Indoor air temperature: 14.0 °CWB 16.0 °CWB...
  • Page 14 ® • Outdoor Unit • VRV III heat recovery, with connection to heating only hydrobox • REYAQ-P Capacity tables 4 - 1 Cooling Capacity Tables REYAQ14P TC: Total Capacity: kW ; PI: Power Input: kW (compressor + outdoor fan motor) Indoor air temperature: 14.0 °CWB 16.0 °CWB...
  • Page 15 ® • Outdoor Unit • VRV III heat recovery, with connection to heating only hydrobox • REYAQ-P Capacity tables 4 - 1 Cooling Capacity Tables REYAQ16P TC: Total Capacity: kW ; PI: Power Input: kW (compressor + outdoor fan motor) Indoor air temperature: 14.0 °CWB 16.0 °CWB...
  • Page 16 ® • Outdoor Unit • VRV III heat recovery, with connection to heating only hydrobox • REYAQ-P Capacity tables 4 - 1 Cooling Capacity Tables REYAQ16P TC: Total Capacity: kW ; PI: Power Input: kW (compressor + outdoor fan motor) Indoor air temperature: 14.0 °CWB 16.0 °CWB...
  • Page 17: Heating Capacity Tables

    ® • Outdoor Unit • VRV III heat recovery, with connection to heating only hydrobox • REYAQ-P Capacity tables 4 - 2 Heating Capacity Tables REYAQ10P TC: Total Capacity: kW ; PI: Power Input: kW (compressor + outdoor fan motor) Indoor air temperature: °CDB Outdoor 16.0...
  • Page 18 ® • Outdoor Unit • VRV III heat recovery, with connection to heating only hydrobox • REYAQ-P Capacity tables 4 - 2 Heating Capacity Tables REYAQ10P TC: Total Capacity: kW ; PI: Power Input: kW (compressor + outdoor fan motor) Indoor air temperature: °CDB Outdoor 16.0...
  • Page 19 ® • Outdoor Unit • VRV III heat recovery, with connection to heating only hydrobox • REYAQ-P Capacity tables 4 - 2 Heating Capacity Tables REYAQ12P TC: Total Capacity: kW ; PI: Power Input: kW (compressor + outdoor fan motor) Indoor air temperature: °CDB Outdoor 16.0...
  • Page 20 ® • Outdoor Unit • VRV III heat recovery, with connection to heating only hydrobox • REYAQ-P Capacity tables 4 - 2 Heating Capacity Tables REYAQ12P TC: Total Capacity: kW ; PI: Power Input: kW (compressor + outdoor fan motor) Indoor air temperature: °CDB Outdoor 16.0...
  • Page 21 ® • Outdoor Unit • VRV III heat recovery, with connection to heating only hydrobox • REYAQ-P Capacity tables 4 - 2 Heating Capacity Tables REYAQ14P TC: Total Capacity: kW ; PI: Power Input: kW (compressor + outdoor fan motor) Indoor air temperature: °CDB Outdoor 16.0...
  • Page 22 ® • Outdoor Unit • VRV III heat recovery, with connection to heating only hydrobox • REYAQ-P Capacity tables 4 - 2 Heating Capacity Tables REYAQ14P TC: Total Capacity: kW ; PI: Power Input: kW (compressor + outdoor fan motor) Indoor air temperature: °CDB Outdoor 16.0...
  • Page 23 ® • Outdoor Unit • VRV III heat recovery, with connection to heating only hydrobox • REYAQ-P Capacity tables 4 - 2 Heating Capacity Tables REYAQ16P TC: Total Capacity: kW ; PI: Power Input: kW (compressor + outdoor fan motor) Indoor air temperature: °CDB Outdoor 16.0...
  • Page 24 ® • Outdoor Unit • VRV III heat recovery, with connection to heating only hydrobox • REYAQ-P Capacity tables 4 - 2 Heating Capacity Tables REYAQ16P TC: Total Capacity: kW ; PI: Power Input: kW (compressor + outdoor fan motor) Indoor air temperature: °CDB Outdoor 16.0...
  • Page 25: Capacity Correction Factor

    ® • Outdoor Unit • VRV III heat recovery, with connection to heating only hydrobox • REYAQ-P Capacity tables 4 - 3 Capacity Correction Factor REYAQ10P 1. Rate of change in heating capacity 2. Rate of change in cooling capacity Equivalent piping length (m) Equivalent piping length (m) [Explanation of symbols]...
  • Page 26 ® • Outdoor Unit • VRV III heat recovery, with connection to heating only hydrobox • REYAQ-P Capacity tables 4 - 3 Capacity Correction Factor REYAQ12P 1. Rate of change in heating capacity 2. Rate of change in cooling capacity Equivalent piping length (m) Equivalent piping length (m) [Explanation of symbols]...
  • Page 27 ® • Outdoor Unit • VRV III heat recovery, with connection to heating only hydrobox • REYAQ-P Capacity tables 4 - 3 Capacity Correction Factor REYAQ14P 1. Rate of change in heating capacity 2. Rate of change in cooling capacity Equivalent piping length (m) Equivalent piping length (m) [Explanation of symbols]...
  • Page 28 ® • Outdoor Unit • VRV III heat recovery, with connection to heating only hydrobox • REYAQ-P Capacity tables 4 - 3 Capacity Correction Factor REYAQ16P 1. Rate of change in heating capacity 2. Rate of change in cooling capacity Equivalent piping length (m) Equivalent piping length (m) [Explanation of symbols]...
  • Page 29: Dimensional Drawings

    ® • Outdoor Unit • VRV III heat recovery, with connection to heating only hydrobox • REYAQ-P Dimensional drawings 5 - 1 Dimensional Drawings ® • VRV Systems • Outdoor Unit...
  • Page 30: Centre Of Gravity

    ® • Outdoor Unit • VRV III heat recovery, with connection to heating only hydrobox • REYAQ-P Centre of gravity 6 - 1 Centre of Gravity ® • VRV Systems • Outdoor Unit...
  • Page 31: Piping Diagrams

    ® • Outdoor Unit • VRV III heat recovery, with connection to heating only hydrobox • REYAQ-P Piping diagrams 7 - 1 Piping Diagrams ® • VRV Systems • Outdoor Unit...
  • Page 32: Wiring Diagrams

    ® • Outdoor Unit • VRV III heat recovery, with connection to heating only hydrobox • REYAQ-P Wiring diagrams 8 - 1 Wiring Diagrams - Three Phase ® • VRV Systems • Outdoor Unit...
  • Page 33 ® • Outdoor Unit • VRV III heat recovery, with connection to heating only hydrobox • REYAQ-P Wiring diagrams 8 - 1 Wiring Diagrams - Three Phase ® • VRV Systems • Outdoor Unit...
  • Page 34: External Connection Diagrams

    ® • Outdoor Unit • VRV III heat recovery, with connection to heating only hydrobox • REYAQ-P External connection diagrams 9 - 1 External Connection Diagrams ® • VRV Systems • Outdoor Unit...
  • Page 35: Sound Data

    ® • Outdoor Unit • VRV III heat recovery, with connection to heating only hydrobox • REYAQ-P Sound data 10 - 1 Sound Power Spectrum REYAQ10P REYAQ12P Octave band center frequency (Hz) Octave band center frequency (Hz) 3TW59927-2A 3TW59927-2A REYAQ14P REYAQ16P Octave band center frequency (Hz) Octave band center frequency (Hz)
  • Page 36: Sound Pressure Spectrum

    ® • Outdoor Unit • VRV III heat recovery, with connection to heating only hydrobox • REYAQ-P Sound data 10 - 2 Sound Pressure Spectrum REYAQ10P REYAQ12P Approximate Approximate threshold hearing threshold hearing for continuous for continuous noise noise Octave band center frequency (Hz) Octave band center frequency (Hz) 3TW59927-1A 3TW59927-1A...
  • Page 37: Installation

    ® • Outdoor Unit • VRV III heat recovery, with connection to heating only hydrobox • REYAQ-P Installation 11 - 1 Refrigerant Pipe Selection Selection of piping size C. Piping between refrigerant branch kit or branch selector box and indoor unit Pipe size for direct connection to indoor unit must be the same NOTICE as the connection size of the indoor unit.
  • Page 38 ® • Outdoor Unit • VRV III heat recovery, with connection to heating only hydrobox • REYAQ-P Installation 11 - 1 Refrigerant Pipe Selection For refnets joints other than the first branch (example refnet joint b and c), select the proper branch kit model based on the Maximum allowable lengths total capacity index of all indoor units connected after the refrigerant branch.
  • Page 39: Operation Range

    ® • Outdoor Unit • VRV III heat recovery, with connection to heating only hydrobox • REYAQ-P Operation range 12 - 1 Operation Range REYAQ-P Heating mode Cooling mode Indoor temperature (°CDB) Indoor temperature (°CDB) Remark Operation range is valid for combination of REYAQ-P and direct expansion indoor units. 3TW60653-1A(2) ®...
  • Page 40 All content is copyrighted by Daikin Europe N.V.. Naamloze Vennootschap - Zandvoordestraat 300, B-8400 Oostende - Belgium - www.daikin.eu - BE 0412 120 336 - RPR Oostende Naamloze Vennootschap - Zandvoordestraat 300, B-8400 Oostende - Belgium - www.daikin.eu - BE 0412 120 336 - RPR Oostende...