Daikin RXYQ96PYDN Service Manual page 282

R-410a heat pump 60hz, r-410a heat recovery 60hz
Hide thumbs Also See for RXYQ96PYDN:
Table of Contents

Advertisement

SiUS34-801A_b
<REYQ144 to 240PYDN, REYQ168 to 240PTJU>
Cancel the disable-operation setting by each outdoor unit.
Make the following setting on the outdoor unit 1.
(If this setting is made on an outdoor unit other than the outdoor unit 2, the setting will become
invalid.)
following diagram:
Outdoor unit 1:
Outdoor unit 2:
8
Set No. 38 Disable outdoor unit 1 operation of setting mode 2 to [OFF].
(Step)
(1) Press and hold the PAGE button (BS1)
(2) Press the SET button (BS2) 38 times.
(3) Press the RETURN button (BS3) once.
(4) Press the SET button (BS2) once.
(5) Press the RETURN button (BS3) twice.
(6) Press the MODE button (BS1) once.
8
Set No. 39 Disable outdoor unit 2 operation of setting mode 2 to [OFF].
(Step)
(1) Press the MODE button (BS1) for 5
(2) Press the SET button (BS2) 39 times.
(3) Press the RETURN button (BS3) once.
(4) Press the SET button (BS2) once.
(5) Press the RETURN button (BS3) twice.
(6) Press the MODE button (BS1) once.
VRVIII R-410A Heat Recovery 60Hz
* You can determine the outdoor units 1 and 2 according to the LED displays shown in the
LED display (
: ON,
: OFF,
8
1
H1P-----------H7P H8P
1181111 8
1111111 9
Cancel disabling the outdoor unit 1 from operating:
for 5 sec. or more.
Cancel disabling the outdoor unit 2 from operating:
seconds or more.
: Blink)
9
LED display (
: ON,
8
H1P-----------H7P
8111111
8811881
8111191
(Factory setting)
8111119
8111111
1181111
LED display (
: ON,
8
H1P-----------H7P
8111111
8811888
8111191
(Factory setting)
8111119
8111111
1181111
: OFF,
: Blink)
1
9
: OFF,
: Blink)
1
9
Field Setting
267

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents