Field Setting
(9) Setting of operation mode to [AUTO]
This setting makes it possible to change differential values for mode selection while in automatic
operation mode.
The automatic operation mode setting is made by the use of the [Operation Mode Selector]
button.
(10) Auto Restart after Power Failure Reset
For the air conditioners with no setting for the Auto Restart after Power Failure Reset function
(same as factory setting), the units will be left in the stop condition when the power supply is reset
automatically after power failure reset or if the main power supply is turned off and then on again.
For air conditioners that do have this setting, the units may start automatically after power failure
reset or if the main power supply is turned on again, and return to prior normal operation.
When the unit is set to enable [Auto restart function after power failure reset], use the following
cautions:
Caution 1. The air conditioner starts operation suddenly after power failure reset or
(11) Air Flow When Cooling Thermostat is OFF
Sets airflow to [LL air flow] when cooling thermostat is OFF.
(12) Setting of Normal Air Flow
Make the following setting according to the ceiling height. The setting position No. is set to [01] at
the factory.
306
Mode No.
Setting switch No.
12 (22)
4
the main power supply turned on again. 2. During service work, turning
off the main power switch while the unit is in operation, and turning on
the switch again after the work is completed starts operation (the fan
rotates).
Mode No.
12 (22)
In the Case of FXAQ, FXHQ
Setting Switch
Mode No.
No.
13(23)
0
01
02
03
0°F
1.8°F
2.6°F
First Code No.
Second Code No.
6
Setting Position
No.
01
Wall-mounted type: Standard
02
Wall-mounted type: Slight increase
03
Wall-mounted type: Normal increase
Setting position No.
04
05
06
5.4°F
7.2°F
9.0°F 10.8°F 12.6°F
Contents
01
LL airflow
02
Preset airflow
Setting
SiUS34-801A_b
07
08
Indoor Unit