Daikin RXYQ96PYDN Service Manual page 132

R-410a heat pump 60hz, r-410a heat recovery 60hz
Hide thumbs Also See for RXYQ96PYDN:
Table of Contents

Advertisement

SiUS34-801A_b
<RXYQ144, 168, 192, 216, 240PYDN, RXYQ168, 192, 216, 240PTJU>
Cancel the disable-operation setting by each outdoor unit.
Make the following setting on the outdoor unit 1. If this setting is made on an outdoor unit other than
the outdoor unit 2, the setting will become invalid.
8
Set No. 38 Disable outdoor unit 1 operation of setting mode 2 to OFF.
8
Set No. 39 Disable-outdoor-unit-2 operation of setting mode 2 to OFF.
VRVIII R-410A Heat Pump 60Hz
*It is possible to tell the outdoor units 1 and 2 according the LED displays shown below.
LED display (
H1P-----------H7P H8P
Outdoor unit 1:
1181111 8
Outdoor unit 2:
1111111 9
Cancel disabling the outdoor unit 1 from operating:
(Step)
(1) Press and hold the MODE button (BS1)
for 5 sec. or more.
(2) Press the SET button (BS2) 38 times.
(3) Press the RETURN button (BS3) once.
(4) Press the SET button (BS2) once.
(5) Press the RETURN button (BS3) twice.
(6) Press the MODE button (BS1) once.
Cancel disabling the outdoor unit 2 from operating:
(Step)
(1) Press the MODE button (BS1) for 5
seconds or more.
(2) Press the SET button (BS2) 39 times.
(3) Press the RETURN button (BS3) once.
(4) Press the SET button (BS2) once.
(5) Press the RETURN button (BS3) twice.
(6) Press the MODE button (BS1) once.
: ON,
: OFF,
: Blink)
8
1
9
LED display (
H1P-----------H7P
8111111
8811881
8111191
8111119
8111111
1181111
LED display (
H1P-----------H7P
8111111
8811888
8111191
8111119
8111111
1181111
Field Settings
: ON,
: OFF,
: Blink)
8
1
9
(Factory setting)
: ON,
: OFF,
: Blink)
8
1
9
(Factory setting)
117

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents