Field Setting
12.1.4 Setting Contents and Code No. – VRV Indoor unit
Mode
Setting
No.
Switch
No.
Note 2
Filter contamination heavy/
light (Setting for display
time to clean air filter)
0
(Sets display time to clean
air filter to half when there
is heavy filter
contamination.)
10(20)
1
Long-life filter type
2
Thermostat sensor in remote controller
Display time to clean air filter calculation
3
(Set when filter sign is not to be displayed.)
Optional accessories output selection (field
0
selection of output for adaptor for wiring)
ON/OFF input from outside (Set when ON/
1
OFF is to be controlled from outside.)
Thermostat differential changeover
2
VRV
(Set when remote sensor is to be used.)
system
12(22)
Air flow setting when heating thermostat is
indoor
3
OFF
unit
settings
Automatic mode differential (automatic
4
temperature differential setting for VRV
system heat recovery series cool/heat)
5
Power failure automatic reset
Air flow setting when Cooling thermostat is
6
OFF
0
Setting of normal air flow
Selection of air flow direction
1
(Set when a blocking pad kit has been
installed.)
3
Operation of downward flow flap: Yes/No
13(23)
4
Field set air flow position setting
5
Setting of static pressure selection
1
Thermostat OFF excess humidity
Direct duct connection
(when the indoor unit and heat reclaim
2
ventilation unit are connected by duct
directly.) ∗Note 6
15(25)
3
Drain pump humidifier interlock selection
Field set selection for individual ventilation
5
setting by remote controller
Notes :
1. Settings are made simultaneously for the entire group, however, if you select the mode No.
2. The mode numbers inside parentheses cannot be used by wireless remote controllers, so they
3. Marked
4. Do not make settings other than those described above. Nothing is displayed for functions the
5. [88] may be displayed to indicate the remote controller is resetting when returning to the normal
6. If the setting mode to [Equipped] the heat reclaim ventilation fan conducts the fan residual
302
Setting Contents
Super long
life filter
Long-life filter
Standard
filter
inside parentheses, you can also set by each individual unit. Setting changes cannot be
checked except in the individual mode for those in parentheses.
cannot be set individually. Setting changes also cannot be checked.
are factory set.
indoor unit is not equipped with.
mode.
operation by linking to indoor unit.
Second Code No.(Note 3)
01
02
Approx.
Approx.
10,000
hrs.
Approx.
Approx.
Light
2,500
Heavy
hrs.
Approx.
Approx.
200
hrs.
Long-life filter
Super long-life filter
Remote
Only body
controller + Body
thermostat
thermostat
Display
No display
Indoor unit
turned ON by
thermostat
Forced OFF
ON/OFF control
1.8°F
0.9°F
LL
Set fan speed
01:0
02:1
03:2
Not equipped
Equipped
LL
Set fan speed
N
H
F (4 directions)
T (3 directions)
Equipped
Not equipped
Draft prevention
Standard
High static
Standard
pressure
Not equipped
Equipped
Not equipped
Equipped
Not equipped
Equipped
Not equipped
Equipped
SiUS34-801A_b
03
5,000
hrs.
1,250
hrs.
100
hrs.
Only remote
controller
thermostat
Operation
Malfunction
output
output
External
protection
device input
04:3
05:4
06:5
07:6
S
W (2
directions)
Ceiling
Soiling
prevention
Details
No
04
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
08:7
(10)
(11)
(12)
(13)
(14)
(15)
(16)
(17)
(18)
(19)
(20)
Indoor Unit