Special Control
7.3.2 Heating Oil Return Operation (including cooling / heating simultaneous
operation)
[Start conditions]
Referring to the following conditions, start heating oil return operation.
• Integral oil rise rate is reached to specified level.
OR
• When cumulative compressor operating time exceeds 8 hours (2 hours when the power supply turns ON for the
first time)
Furthermore, the integral oil rise rate is calculated by Tc, Te, and compressor loads.
The higher the compressor operating step No., the cumulative refrigerant oil consumption increases.
Actuator
Compressor 1
Compressor 2
Outdoor unit fan 1
Outdoor unit fan 2
Electronic expansion valve (main)
Electronic expansion valve
(subcooling)
Electronic expansion valve (refilling
refrigerant)
Four-way valve (for heat changer
selection)
Four-way valve (for high- and low-
pressure gas pipe selection)
Solenoid valve (main bypass)
Solenoid valve (hot gas)
Solenoid valve (liquid pipe of
refrigerant regulator)
Solenoid valve (gas discharge pipe of
refrigerant regulator)
Solenoid valve (drain pipe of
refrigerant regulator)
Solenoid valve (discharge pipe of
refrigerant regulator)
End conditions
*1: In case of multi outdoor unit system:
Master unit: It conducts the operation listed in the table above.
Slave units: Operating units conduct the operation listed in the table above.
Non-operating units conduct the operation listed in the table above after the Oil Returning process. Non-
operating units stop while in Preparation mode.
202
Elect. symbol
Symbol
REYQ REMQ
M1C Maintain load that was applied before oil return operation.
M1C
M2C
M2C
M1F
M1F
M2F
M2F
Y1E
EVM
Y1E
Y3E
Y2E
EVT
Y3E
Y5E
EVJ
Y4E
Y2E
Y2S
20SA
Y3S
Y9S
20SB
Y8S
Y2S
Y5S
SVE
Y6S
Y10S
SVP
Y4S
Y5S
SVL
Y3S
Y4S
SVG
Y1S
Y1S
SVO
Y7S
Y7S
SVT
Y6S
Y8S
Oil return operation
When current circulation rate < circulation rate required for
oil return operation, turn ON the STD compressor every 10
seconds (up to 3 units at maximum).
When outdoor unit heat exchanger is condenser, the fan
will run under cooling fan control.
When outdoor unit heat exchanger is evaporator, the fan
will run at the fan step 7 or 8.
20SA=ON : PI control
20SA=OFF : 418pls
PI control
80pls
When outdoor unit heat exchanger is condenser, the valve
will turn OFF.
When outdoor unit heat exchanger is evaporator, the valve
will turn ON.
OFF
OFF
0pls
0pls
0pls
0pls
0pls
• Pe_min<31.9psi
or
• After a lapse of 9 min.
VRVIII R-410A Heat Recovery 60Hz
SiUS34-801A_b