SiUS34-801A_b
Troubleshooting
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Diagnosis Flow 5
Check 3
Check 4
Is the model BSVQ-P
connected?
YES
Diagnosis Flow 6
Check 3
Check 4
Is the wiring
between the outdoor unit
and the BS unit
correct?
YES
Troubleshooting by Indication on the Remote Controller
NO
NO
Connect the model BSVQ-P.
Replace the outdoor unit PC board
as shown below.
• With single systems, replace the
control PC board 1 (A1P).
• With multi systems, replace the
main PC board (A1P).
Correct the wiring.
Replace the outdoor unit PC board
as shown below.
• With single systems, replace the
control PC board 1 (A1P).
• With multi systems, replace the
main PC board (A1P).