SiUS34-801A_b
STD compressor ON
Demand to operate.
STD compressor OFF for 30 min.*
When occurring 3 times within 90 min.,
the malfunction code " E6 " is output.
VRVIII R-410A Heat Recovery 60Hz
CT detection current value>15.0A
34 (230V)
*If the power supply is reset while in
operation prohibition mode, the prohibition
timer will continue counting when the
(460)
power supply is turned ON.
Protection Control
217