SiUS34-801A_b
b. Setting mode 2
Push and hold the MODE (BS1)
button for 5 seconds and set to
Setting mode 2.
<Selection of setting items>
Push the SET (BS2) button and set
the LED display to a setting item
shown in the table on the right.
¯
Push the RETURN (BS3) button and
decide the item. (The present setting
condition is blinked.)
<Selection of setting conditions>
Push the SET (BS2) button and set
to the setting condition you want.
¯
Push the RETURN (BS3) button and
decide the condition.
Push the RETURN (BS3) button and
set to the initial status of Setting
mode 2.
* If you become unsure of how to
proceed, push the MODE (BS1)
button and return to setting mode 1.
VRVIII R-410A Heat Recovery 60Hz
No.
Setting item
Digital pressure
0
gauge kit display
Cool/heat unified
1
address
Low noise/demand
2
address
Test operation
3
settings
Indoor unit forced
5
fan H
Indoor unit forced
6
operation
8
Te setting
9
Tc setting
10 Defrost changeover
setting
11 Sequential
operation setting
External low noise
12
setting / Demand
setting
13 AIRNET address
18 High static pressure
setting
Additional
20
refrigerant charge
operation setting
Refrigerant recovery/
21
vacuuming mode
setting
22 Night-time low
noise setting
24 ENECUT test
operation
25 Setting of external
low noise level
Night-time low
26
noise operation
start setting
Night-time low
27
noise operation end
setting
Power transistor
check mode
∗Check after
(V2764)
28
disconnection of
compressor wires
29 Capacity
precedence setting
30 Demand setting 1
32 Normal demand
setting
Description
Used to make setting of contents to display on the digital
pressure gauges (e.g. pressure sensors and temperature
sensors)
Sets address for cool/heat unified operation.
Address for low noise/demand operation
Used to conduct test operation without making changes to
the PC board and replacing the refrigerant, after the
completion of maintenance.
Allows forced operation of indoor unit fan while unit is
stopped. (H tap)
Allows forced operation of indoor unit.
(Forced thermostat ON)
Target evaporation temperature for cooling
Target condensation temperature for heating
Changes the temperature condition for defrost and sets to
quick defrost or slow defrost.
Sets sequential operation
(Factory set to ON)
Reception of external low noise or demand signal
Set address for AIRNET.
Make this setting in the case of operating in high static
pressure mode with diffuser duct mounted.
In order to mount the diffuser duct, remove the cover from the
outdoor unit fan.
Carries out additional refrigerant charge operation.
Sets to refrigerant recovery or vacuuming mode.
Sets automatic nighttime low noise operation in a simple way.
The operating time is based on "Starting set" and "Ending
set".
Used to forcibly turn ON the ENECUT. (Be noted that the
ENECUT is only functional with outdoor unit in the stopped
state - Japanese domestic model only.)
Sets low noise level when the low noise signal is input from
outside.
Sets starting time of nighttime low noise operation.
(Night-time low noise setting is also required.)
Sets ending time of nighttime low noise operation.
(Night-time low noise setting is also required.)
Used for trouble diagnosis of DC compressor. Since the
waveform of inverter is output without wiring to the
compressor, it is convenient to probe whether the trouble
comes from the compressor or PC board.
If the capacity control is required, the low noise control is
automatically released by this setting during carrying out low
noise operation and nighttime low noise operation.
Changes target value of power consumption when demand
control 1 is input.
Normally enables demand control 1 without external input.
(Effective to prevent a problem caused by a circuit breaker
of small capacity shutting down due to large load.)
Field Setting