Daikin RXYQ96PYDN Service Manual page 215

R-410a heat pump 60hz, r-410a heat recovery 60hz
Hide thumbs Also See for RXYQ96PYDN:
Table of Contents

Advertisement

Special Control
The higher the compressor operating step No., the cumulative refrigerant oil consumption increases.
Outdoor unit actuator
Compressor 1
Compressor 2
Outdoor unit fan 1
Outdoor unit fan 2
Four-way valve (for heat
exchanger selection)
Four-way valve (for high-
and low-pressure gas
pipe selection)
Electronic expansion
valve (main)
Electronic expansion
valve (subcooling)
Electronic expansion
valve (refilling refrigerant)
Solenoid valve (main
bypass)
Solenoid valve (hot gas)
Solenoid valve (liquid
pipe of refrigerant
regulator)
Solenoid valve (gas
discharge pipe of
refrigerant regulator)
Solenoid valve (drain pipe
of refrigerant regulator)
Solenoid valve (discharge
pipe of refrigerant
regulator)
End conditions
*1: In case of multi outdoor unit system:
Master unit: It conducts the operation listed in the table above.
Slave units: Operating units conduct the operation listed in the table above.
Non-operating units conduct the operation listed in the table above after the Oil Returning process. (Non-
operating units stop while in Preparation mode.)
200
Elect. symbol
Symbol
REYQ REMQ
M1C
M1C
M2C
M2C
M1F
M1F
M2F
M2F
Y2S
20SA
Y3S
Y9S
20SB
Y8S
Y2S
Y1E
EVM
Y1E
Y3E
Y2E
EVT
Y3E
Y5E
EVJ
Y4E
Y2E
Y5S
SVE
Y6S
Y10S
SVP
Y4S
Y5S
SVL
Y3S
Y4S
SVG
Y1S
Y1S
SVO
Y7S
Y7S
SVT
Y6S
Y8S
Oil return operation
52Hz+ON
(Subsequently, constant low
pressure control)
Maintain the number of
compressors that were used before
oil return operation)
Cooling fan control
OFF
ON
1375pls
SH control
80pls
ON
OFF
0pls
0pls
0pls
0pls
• After a lapse of 5 min.
or
• TsA - Te<41°F
SiUS34-801A_b
Operation after oil return
52Hz+ON
(Subsequently, constant low
pressure control)
Maintain the number of
compressors that were used before
oil return operation)
Cooling fan control
OFF
ON
1375pls
SH control
80pls
ON
OFF
0pls
0pls
0pls
0pls
• After a lapse of 3 min.
• Pe_min<41°F
or
• Pc_max>526.35 psi
• HTdmax>212°F
VRVIII R-410A Heat Recovery 60Hz