Test Operation
10.3.3 When an Indoor Unit or Outdoor Unit has been Added, or Indoor or
Outdoor Unit PC Board has been Changed
Be sure to push and hold the RESET button for 5 seconds. If not, the addition cannot be
recognized. In this case, the unit cannot be run for up to 12 minutes to automatically set the
address (indoor-outdoor address, etc.)
Status
Outdoor unit
Indoor unit
92
Test lamp H2P .... ON
Can also be set during operation described above.
If the ON button is pushed during operation described above, the [UH] or [U4]
malfunction indicator blinks. It returns to normal when the automatic setting is
complete.
[R-410A] Label
[R-410A] Label
< RXYQ144PTJU Only >
Electrical
Components
Box cover
Electrical Components Box (upper right)
SiUS34-801A_b
VRVIII R-410A Heat Pump 60Hz