List of Electrical and Functional Parts

3. List of Electrical and Functional Parts
3.1

Outdoor Unit

3.1.1 RXYQ72P, 96P, 120PYDN
Item
Inverter
Compressor
STD 1
Fan motor
Electronic expansion valve (Main)
Electronic expansion valve (Refrigerant charge)
Electronic expansion valve (Subcool)
High pressure
Pressure
switch
protection
Low pressure sensor
Discharge gas temperature
protection
(Discharge pipe thermistor)
Temperature
protection
Inverter fin temperature
protection
(Radiator fin thermistor)
Others
Fuse
510
Name
Symbol
Type
M1C
OC protection
device
Type
M2C
OC protection
device
OC protection
M1F
device
Y1E
Y2E
Y3E
For M1C
S1PH
For M2C
S2PH
SENPL
R3T
R1T
F1U
For main PC
board
F2U
For Noise filter
F1U
PC board
Model
JT1GCVDKYR@SA
14.7A
JT170G-KYE@T
15.0A
3.0A
Fully closed : 0pls
Fully closed : 0pls
Fully closed : 0pls
+0
OFF : 580
psi
−17.40
+0
OFF : 580
psi
−17.40
OFF : 10.15psi
OFF : 275°F
OFF : 199.4°F
Time-lag 3.15A AC 250V / 250V AC 10A Class B
Time-lag 3.15A AC 250V / 250V AC 10A Class B
250V AC 5A Class B
SiUS34-801A_b
Fully open : 480pls
Fully open : 480pls
Fully open : 480pls
ON : 435±21.75psi
ON : 435±21.75psi