Large Capacity Start Up Control (Heating) - Daikin RXYQ96PYDN Service Manual

R-410a heat pump 60hz, r-410a heat recovery 60hz
Hide thumbs Also See for RXYQ96PYDN:
Table of Contents

Advertisement

Special Control
7.1.2 Startup Control in Heating Operation
Actuator
Compressor 1
Compressor 2
Outdoor unit fan 1
Outdoor unit fan 2
Electronic expansion
valve (Main)
Electronic expansion
valve (Subcooling)
Electronic expansion
valve (Refrigerant
charge)
Four-way valve
(Heat exchanger switch)
Four-way valve (High/low
pressure gas pipe switch)
Solenoid valve (Main
bypass)
Solenoid valve (Hot gas)
Solenoid valve
(Refrigerant regulator
liquid pipe)
Solenoid valve
(Refrigerant regulator gas
vent pipe)
Solenoid valve
(Refrigerant regulator
exhaust pipe)
Solenoid valve
(Refrigerant regulator
discharge pipe)
Ending conditions
7.2

Large Capacity Start Up Control (Heating)

For startup, oil return operation, or setup after defrosting, start up multiple compressors at a high speed according to the
198
Elect.
Control
symbol
Symbol
REYQ
REMQ
M1C M1C
0 Hz
M2C M2C
M1F
M1F
STEP4
M2F
M2F
Y1E
EVM
Y1E 0 pls
Y3E
Y2E
EVT
Y3E 0 pls
Y5E
EVJ
Y4E
Y2E 80 pls
When
outdoor
heat
exchanger
is
evaporator:
Y2S
ON
20SA
Y3S
Y9S
When
outdoor
heat
exchanger
is
condenser:
OFF
20SB
Y8S
Y2S OFF
Y5S
SVE
Y6S OFF
Y10S
SVP
Y4S
Y5S OFF
SVL
Y3S
Y4S OFF
SVG
Y1S
Y1S OFF
SVO
Y7S
Y7S OFF
SVT
Y6S
Y8S OFF
A lapse of
60 sec.
before
startup
STEP1
52 Hz+OFF
20SA=ON: STEP7
20SA=OFF
+1step/15 sec. (When
Pc_max>313.2 psi)
-1step/15 sec. (When
Pc_max<256.65 psi)
20SA=ON: SH Control
20SA=OFF: 1375 pls
0 pls
80 pls
When outdoor heat exchanger
is evaporator: ON
When outdoor heat exchanger
is condenser: OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
A lapse of 15 sec.
SiUS34-801A_b
Startup control
STEP2
52Hz+OFF+2STEP / 20 sec.
(Until it reaches
Pc-Pe>56.55 psi)
20SA=ON: STEP7
20SA=OFF
+1step/15 sec. (When
Pc_max>313.2 psi)
-1step/15 sec. (When
Pc_max<256.65 psi)
20SA=ON: SH Control
20SA=OFF: 1375 pls
0 pls
80 pls
When outdoor heat exchanger
is evaporator: ON
When outdoor heat exchanger
is condenser: OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
• A lapse of 90 sec.
OR
• Pc - Pe>56.55 psi
VRVIII R-410A Heat Recovery 60Hz