Set Up The Meter - Siemens ACCESS 9340 Reference Manual

Table of Contents

Advertisement

ACCESS 9340 and 9360 Meters
Chapter 3—Operation

Set Up the Meter

EN–16
This section explains how to setup a meter using a display. To
configure a meter without a display use ION Setup.
NOTE: If you are setting up the meter using ION Setup, it is
recommended you set up communications first. The default settings
are 1) Protocol: Modbus RTU, 2) Address: 1, 3) Baud rate: 9600, and
4) Parity: Even (if you are using a serial connection to communicate
with the meter while using ION Setup, set the Parity to None).
To begin meter setup, do the following:
1. Scroll through the Level 1 menu list until you see MAINT.
2. Press MAINT.
3. Press SETUP.
4. Enter your password.
NOTE: The default password is 0000.
5. To save the changes, press
appears, then press YES.
Follow the directions in the following sections to set up the meter.