Information List - Siemens SIPROTEC 4 7VK61 Manual

Breaker management device
Table of Contents

Advertisement

Functions
2.2 Automatic reclosure function (optional)
Addr.
Parameter
3470
2.AR: CB? CLOSE
3471
2.AR SynRequest
3472
3.AR: START
3473
3.AR: T-ACTION
3475
3.AR Tdead 1Flt
3476
3.AR Tdead 2Flt
3477
3.AR Tdead 3Flt
3478
3.AR Tdead1Trip
3479
3.AR Tdead3Trip
3480
3.AR: Tdead EV.
3481
3.AR: CB? CLOSE
3482
3.AR SynRequest
3483
4.AR: START
3484
4.AR: T-ACTION
3486
4.AR Tdead 1Flt
3487
4.AR Tdead 2Flt
3488
4.AR Tdead 3Flt
3489
4.AR Tdead1Trip
3490
4.AR Tdead3Trip
3491
4.AR: Tdead EV.
3492
4.AR: CB? CLOSE
3493
4.AR SynRequest

Information List

2.2.4
No.
Information
2701
>AR on
2702
>AR off
2703
>AR block
2711
>AR Start
2712
>Trip L1 AR
2713
>Trip L2 AR
2714
>Trip L3 AR
2715
>Trip 1pole AR
2716
>Trip 3pole AR
2727
>AR RemoteClose
2731
>Sync.release
66
Setting Options
YES
NO
YES
NO
YES
NO
0.01 .. 300.00 sec
0.01 .. 1800.00 sec
0.01 .. 1800.00 sec
0.01 .. 1800.00 sec
0.01 .. 1800.00 sec
0.01 .. 1800.00 sec
0.01 .. 1800.00 sec
YES
NO
YES
NO
YES
NO
0.01 .. 300.00 sec
0.01 .. 1800.00 sec
0.01 .. 1800.00 sec
0.01 .. 1800.00 sec
0.01 .. 1800.00 sec
0.01 .. 1800.00 sec
0.01 .. 1800.00 sec
YES
NO
YES
NO
Type of
Comments
Informa-
tion
SP
>AR: Switch on auto-reclose function
SP
>AR: Switch off auto-reclose function
SP
>AR: Block auto-reclose function
SP
>External start of internal Auto reclose
SP
>AR: External trip L1 for AR start
SP
>AR: External trip L2 for AR start
SP
>AR: External trip L3 for AR start
SP
>AR: External 1pole trip for AR start
SP
>AR: External 3pole trip for AR start
SP
>AR: Remote Close signal
SP
>AR: Sync. release from ext. sync.-check
Default Setting
Comments
NO
CB ready interrogation before
reclosing
NO
Request for synchro-check after
3pole AR
NO
AR start allowed in this cycle
0.20 sec
Action time
1.20 sec
Dead time after 1phase faults
1.20 sec
Dead time after 2phase faults
0.50 sec
Dead time after 3phase faults
2147483647 sec
Dead time after 1pole trip
0.50 sec
Dead time after 3pole trip
1.20 sec
Dead time after evolving fault
NO
CB ready interrogation before
reclosing
NO
Request for synchro-check after
3pole AR
NO
AR start allowed in this cycle
0.20 sec
Action time
1.20 sec
Dead time after 1phase faults
1.20 sec
Dead time after 2phase faults
0.50 sec
Dead time after 3phase faults
2147483647 sec
Dead time after 1pole trip
0.50 sec
Dead time after 3pole trip
1.20 sec
Dead time after evolving fault
NO
CB ready interrogation before
reclosing
NO
Request for synchro-check after
3pole AR
C53000-G1176-C159-5, Edition 05.2018
SIPROTEC 4, 7VK61, Manual