voltage of the switched feeder. This setting does not apply for a close command via the integrated control
functions. If the synchronism check is desired, the device must either feature the integrated synchronism
check function or an external device for synchronism check must be connected.
If the internal synchronism check is to be used, the synchronism check function must be enabled; an addi-
tional voltage U
meterised in the Power System Data 1 (address 210 U4 transformer = Usy2 transf. and the associated
factors).
If no synchronism check is to be performed with manual closing, set MAN. CLOSE = w/o Sync-check. If a
check is desired, set with Sync-check. To not use the MANUAL CLOSE function of the device, set MAN.
CLOSE to NO. This may be reasonable if the close command is output to the circuit breaker without involving
the 7VK61, and the relay itself is not desired to issue a close command.
For commands via the integrated control (on site, DIGSI, serial interface) address 1152 Man.Clos. Imp.
determines whether a close command via the integrated control regarding the MANUAL CLOSE handling for
the protection functions (like instantaneous re-opening when switching onto a fault) is to act like a MANUAL
CLOSE command via binary input. This address also informs the device to which switchgear this applies. You
can select from the switching devices which are available to the integrated control. Select the circuit breaker
which operates for manual closure and, if required, for automatic reclosure (usually Q0). If none is set here, a
CLOSE command via the control will not generate a MANUAL CLOSE impulse for the protection function.
2.1.5.2

Settings

Addresses which have an appended "A" can only be changed with DIGSI, under "Additional Settings".
The table indicates region-specific presettings. Column C (configuration) indicates the corresponding secon-
dary nominal current of the current transformer.
Addr.
Parameter
1103
FullScaleVolt.
1104
FullScaleCurr.
1107
P,Q sign
1130A
PoleOpenCurrent
1131A
PoleOpenVoltage
1135
Reset Trip CMD
1136
OpenPoleDetect.
1150A
SI Time Man.Cl
1151
MAN. CLOSE
1152
Man.Clos. Imp.
SIPROTEC 4, 7VK61, Manual
C53000-G1176-C159-5, Edition 05.2018
for synchronism check has to be connected to the device and this must be correctly para-
sy2
C
Setting Options
1.0 .. 1200.0 kV
10 .. 5000 A
not reversed
reversed
1A
0.05 .. 1.00 A
5A
0.25 .. 5.00 A
2 .. 70 V
CurrentOpenPole
Current AND CB
Pickup Reset
OFF
Current AND CB
w/ measurement
0.01 .. 30.00 sec
with Sync-check
w/o Sync-check
NO
(Einstellmöglichkeiten
anwendungsabhängig)
Default Setting
Comments
400.0 kV
Measurement: Full Scale
Voltage (100%)
1000 A
Measurement: Full Scale
Current (100%)
not reversed
P,Q operational measured
values sign
0.10 A
Pole Open Current
Threshold
0.50 A
30 V
Pole Open Voltage
Threshold
CurrentOpenPole
RESET of Trip Command
w/ measurement
open pole detector
0.30 sec
Seal-in Time after MANUAL
closures
NO
Manual CLOSE COMMAND
generation
none
MANUAL Closure Impulse
after CONTROL
Functions
2.1 General
39