Device; Trip-Dependent Indications - Siemens SIPROTEC 4 7VK61 Manual

Breaker management device
Table of Contents

Advertisement

Functions
2.1 General
Addr.
Parameter
106
VT CONNECTION
107
CT CONNECTION
110
Trip mode
126
Back-Up O/C
133
Auto Reclose
134
AR control mode
135
Synchro-Check
137
U/O VOLTAGE
139
BREAKER FAILURE
140
Trip Cir. Sup.
2.1.2

Device

The device requires some general information. This may be, for example, the type of indication to be issued in
the event a power system fault occurs.
2.1.2.1

Trip-Dependent Indications

Spontaneous Fault Messages
After a fault, the essential fault data spontaneously appear on the device display. Under address 610
FltDisp.LED/LCD you can select whether the spontaneous fault indications are updated in every case of
fault (Target on PU) or only in faults with tripping (Target on TRIP).
28
Setting Options
3phase
1phase
NO
YES
NO
3pole only
1-/3pole
Disabled
TOC IEC
TOC ANSI
TOC IEC /w 3ST
1 AR-cycle
2 AR-cycles
3 AR-cycles
4 AR-cycles
5 AR-cycles
6 AR-cycles
7 AR-cycles
8 AR-cycles
ADT
Disabled
Pickup w/ Tact
Pickup w/o Tact
Trip w/ Tact
Trip w/o Tact
Disabled
Enabled
Disabled
Enabled
Disabled
Enabled
enabled w/ 3I0>
Disabled
1 trip circuit
2 trip circuits
3 trip circuits
Default Setting
Comments
3phase
Voltage transformer connection
YES
Current transformer connection
3pole only
Trip mode
Disabled
Backup overcurrent
Disabled
Auto-Reclose Function
Trip w/ Tact
Auto-Reclose control mode
Disabled
Synchronism and Voltage Check
Disabled
Under / Overvoltage Protection
Disabled
Breaker Failure Protection
Disabled
Trip Circuit Supervision
C53000-G1176-C159-5, Edition 05.2018
SIPROTEC 4, 7VK61, Manual