Function Description; Information List - Siemens SIPROTEC 4 7VK61 Manual

Breaker management device
Table of Contents

Advertisement

2.8.2.1

Function Description

The test programs shown in
device you are using is capable of single-pole tripping.
The output alarms mentioned must be allocated to the relevant command relays that are used for controlling
the circuit breaker coils.
The test is started using the operator panel on the front of the device or using the PC with DIGSI. The proce-
dure is described in detail in the SIPROTEC 4 System Description.
of an open-close test cycle. The set times are those stated in Section
Duration" and "Circuit Breaker Test".
Where the circuit breaker auxiliary contacts indicate the status of the circuit breaker or of its poles to the
device via binary inputs, the test cycle can only be initiated if the circuit breaker is closed.
The information regarding the position of the circuit breakers is not automatically derived from the position
logic according to the above section. For the circuit breaker test function (auto recloser) there are separate
binary inputs for the switching status feedback of the circuit breaker position. These must be taken into
consideration when allocating the binary inputs as mentioned in the previous section.
The alarms of the device show the respective state of the test sequence.
Table 2-7
Serial No.
1
2
3
4
[ein-aus-pruefzyklus-wlk-170902, 1, en_GB]
Figure 2-72

Information List

2.8.2.2
No.
Information
-
CB1tst L1
-
CB1tst L2
-
CB1tst L3
-
CB1tst 123
7325
CB1-TESTtrip L1
7326
CB1-TESTtrip L2
7327
CB1-TESTtrip L3
7328
CB1-TESTtrip123
7329
CB1-TEST close
7345
CB-TEST running
SIPROTEC 4, 7VK61, Manual
C53000-G1176-C159-5, Edition 05.2018
Table 2-7
are available. The single-pole tests are of course only possible if the
Circuit breaker test programs
Test Programs
1-pole TRIP/CLOSE-cycle
phase L1
1-pole TRIP/CLOSE-cycle
phase L2
1-pole TRIP/CLOSE-cycle
phase L3
3-pole TRIP/CLOSE-cycle
Associated close
command
TRIP-CLOSE test cycle
Type of
Informa-
tion
-
-
-
-
OUT
OUT
OUT
OUT
OUT
OUT
2.8 Function Control and Circuit Breaker Test
Figure 2-72
shows the progression over time
2.1.3.1 Setting Notes
Circuit Breaker
CB 1
Comments
CB1-TEST trip/close - Only L1
CB1-TEST trip/close - Only L2
CB1-TEST trip/close - Only L3
CB1-TEST trip/close Phases L123
CB1-TEST TRIP command - Only L1
CB1-TEST TRIP command - Only L2
CB1-TEST TRIP command - Only L3
CB1-TEST TRIP command L123
CB1-TEST CLOSE command
CB-TEST is in progress
Functions
for "Trip Command
Output Indications (No.)
CB1-TESTtrip L1 (7325)
CB1-TESTtrip L2 (7326)
CB1-TESTtrip L3 (7327)
CB1-TESTtrip 123 (7328)
CB1-TEST CLOSE (7329)
159