Addr. Parameter
3481
3.AR: CB? CLOSE
3482
3.AR SynRequest
3483
4.AR: START
3484
4.AR: T-ACTION
3486
4.AR Tdead 1Flt
3487
4.AR Tdead 2Flt
3488
4.AR Tdead 3Flt
3489
4.AR Tdead1Trip
3490
4.AR Tdead3Trip
3491
4.AR: Tdead EV.
3492
4.AR: CB? CLOSE
3493
4.AR SynRequest
3501
FCT Synchronism
3502
Dead Volt. Thr.
3503
Live Volt. Thr.
3504
Umax
3507
T-SYN. DURATION
3508
T SYNC-STAB
3509
SyncCB
3510
Op.mode with AR
3511
AR maxVolt.Diff
3512
AR maxFreq.Diff
3513
AR maxAngleDiff
3515A AR SYNC-CHECK
3516
AR Usy1<Usy2>
3517
AR Usy1>Usy2<
SIPROTEC 4, 7VK61, Manual
C53000-G1176-C159-5, Edition 05.2018
Function
C
Setting Options
Autoreclosure
YES
NO
Autoreclosure
YES
NO
Autoreclosure
YES
NO
Autoreclosure
0.01 .. 300.00 sec
Autoreclosure
0.01 .. 1800.00 sec 1.20 sec
Autoreclosure
0.01 .. 1800.00 sec 1.20 sec
Autoreclosure
0.01 .. 1800.00 sec 0.50 sec
Autoreclosure
0.01 .. 1800.00 sec 2147483647 sec
Autoreclosure
0.01 .. 1800.00 sec 0.50 sec
Autoreclosure
0.01 .. 1800.00 sec 1.20 sec
Autoreclosure
YES
NO
Autoreclosure
YES
NO
Sync. Check
ON
OFF
ON:w/o CloseCmd
Sync. Check
1 .. 100 V
Sync. Check
20 .. 125 V
Sync. Check
20 .. 140 V
Sync. Check
0.01 .. 600.00 sec
Sync. Check
0.00 .. 30.00 sec
Sync. Check
OBJVERWparaMEIN-
STELL
Sync. Check
with T-CB close
w/o T-CB close
Sync. Check
1.0 .. 60.0 V
Sync. Check
0.03 .. 2.00 Hz
Sync. Check
2 .. 80 °
Sync. Check
YES
NO
Sync. Check
YES
NO
Sync. Check
YES
NO
Functions, Settings, Information
Default Setting
Comments
NO
CB ready interrogation
before reclosing
NO
Request for synchro-
check after 3pole AR
NO
AR start allowed in this
cycle
0.20 sec
Action time
Dead time after 1phase
faults
Dead time after 2phase
faults
Dead time after 3phase
faults
Dead time after 1pole trip
Dead time after 3pole trip
Dead time after evolving
fault
NO
CB ready interrogation
before reclosing
NO
Request for synchro-
check after 3pole AR
ON
Synchronism and Voltage
Check function
5 V
Voltage threshold dead
line / bus
90 V
Voltage threshold live
line / bus
110 V
Maximum permissible
voltage
1.00 sec
Maximum duration of
synchronism-check
0.00 sec
Synchronous condition
stability timer
none
Synchronizable circuit
breaker
w/o T-CB close
Operating mode with AR
2.0 V
Maximum voltage differ-
ence
0.10 Hz
Maximum frequency
difference
10 °
Maximum angle differ-
ence
YES
AR at Usy2>, Usy1>, and
Synchr.
NO
AR at Usy1< and Usy2>
NO
AR at Usy1> and Usy2<
E.2 Settings
293