Siemens SIPROTEC 4 7VK61 Manual page 294

Breaker management device
Table of Contents

Advertisement

Functions, Settings, Information
E.2 Settings
Addr. Parameter
3518
AR Usy1<Usy2<
3519
AR OVERRIDE
3530
Op.mode with MC
3531
MC maxVolt.Diff
3532
MC maxFreq.Diff
3533
MC maxAngleDiff
3535A MC SYNCHR
3536
MC Usy1< Usy2>
3537
MC Usy1> Usy2<
3538
MC Usy1< Usy2<
3539
MC OVERRIDE
3701
Uph-e>(>)
3702
Uph-e>
3703
T Uph-e>
3704
Uph-e>>
3705
T Uph-e>>
3709A Uph-e>(>) RESET
3711
Uph-ph>(>)
3712
Uph-ph>
3713
T Uph-ph>
3714
Uph-ph>>
3715
T Uph-ph>>
3719A Uphph>(>) RESET
3721
3U0>(>) (or Ux)
3722
3U0>
3723
T 3U0>
3724
3U0>>
294
Function
C
Setting Options
Sync. Check
YES
NO
Sync. Check
YES
NO
Sync. Check
with T-CB close
w/o T-CB close
Sync. Check
1.0 .. 60.0 V
Sync. Check
0.03 .. 2.00 Hz
Sync. Check
2 .. 80 °
Sync. Check
YES
NO
Sync. Check
YES
NO
Sync. Check
YES
NO
Sync. Check
YES
NO
Sync. Check
YES
NO
Voltage Prot.
OFF
Alarm Only
ON
U>Alarm U>>Trip
Voltage Prot.
1.0 .. 170.0 V
Voltage Prot.
0.00 .. 100.00 sec
Voltage Prot.
1.0 .. 170.0 V
Voltage Prot.
0.00 .. 100.00 sec
Voltage Prot.
0.30 .. 0.99
Voltage Prot.
OFF
Alarm Only
ON
U>Alarm U>>Trip
Voltage Prot.
2.0 .. 220.0 V
Voltage Prot.
0.00 .. 100.00 sec
Voltage Prot.
2.0 .. 220.0 V
Voltage Prot.
0.00 .. 100.00 sec
Voltage Prot.
0.30 .. 0.99
Voltage Prot.
OFF
Alarm Only
ON
U>Alarm U>>Trip
Voltage Prot.
1.0 .. 220.0 V
Voltage Prot.
0.00 .. 100.00 sec
Voltage Prot.
1.0 .. 220.0 V
Default Setting
Comments
NO
AR at Usy1< and Usy2<
NO
Override of any check
before AR
w/o T-CB close
Operating mode with
Man.Cl
2.0 V
Maximum voltage differ-
ence
0.10 Hz
Maximum frequency
difference
10 °
Maximum angle differ-
ence
YES
Manual Close at Usy2>,
Usy1>, and Synchr
NO
Manual Close at Usy1<
and Usy2>
NO
Manual Close at Usy1>
and Usy2<
NO
Manual Close at Usy1<
and Usy2<
NO
Override of any check
before Man.Cl
OFF
Operating mode Uph-e
overvoltage prot.
85.0 V
Uph-e> Pickup
2.00 sec
T Uph-e> Time Delay
100.0 V
Uph-e>> Pickup
1.00 sec
T Uph-e>> Time Delay
0.98
Uph-e>(>) Reset ratio
OFF
Operating mode Uph-ph
overvoltage prot.
150.0 V
Uph-ph> Pickup
2.00 sec
T Uph-ph> Time Delay
175.0 V
Uph-ph>> Pickup
1.00 sec
T Uph-ph>> Time Delay
0.98
Uph-ph>(>) Reset ratio
OFF
Operating mode 3U0 (or
Ux) overvoltage
30.0 V
3U0> Pickup (or Ux>)
2.00 sec
T 3U0> Time Delay (or T
Ux>)
50.0 V
3U0>> Pickup (or Ux>>)
SIPROTEC 4, 7VK61, Manual
C53000-G1176-C159-5, Edition 05.2018

Hide quick links: