Siemens SIPROTEC 4 7VK61 Manual page 295

Breaker management device
Table of Contents

Advertisement

Addr. Parameter
3725
T 3U0>>
3728A 3U0>(>) Stabil.
3729A 3U0>(>) RESET
3731
U1>(>)
3732
U1>
3733
T U1>
3734
U1>>
3735
T U1>>
3739A U1>(>) RESET
3741
U2>(>)
3742
U2>
3743
T U2>
3744
U2>>
3745
T U2>>
3749A U2>(>) RESET
3751
Uph-e<(<)
3752
Uph-e<
3753
T Uph-e<
3754
Uph-e<<
3755
T Uph-e<<
3758
CURR.SUP. Uphe<
3759A Uph-e<(<) RESET
3761
Uph-ph<(<)
3762
Uph-ph<
3763
T Uph-ph<
3764
Uph-ph<<
3765
T Uphph<<
3768
CURR.SUP.Uphph< Voltage Prot.
3769A Uphph<(<) RESET
SIPROTEC 4, 7VK61, Manual
C53000-G1176-C159-5, Edition 05.2018
Function
C
Setting Options
Voltage Prot.
0.00 .. 100.00 sec
Voltage Prot.
ON
OFF
Voltage Prot.
0.30 .. 0.99
Voltage Prot.
OFF
Alarm Only
ON
U>Alarm U>>Trip
Voltage Prot.
2.0 .. 220.0 V
Voltage Prot.
0.00 .. 100.00 sec
Voltage Prot.
2.0 .. 220.0 V
Voltage Prot.
0.00 .. 100.00 sec
Voltage Prot.
0.30 .. 0.99
Voltage Prot.
OFF
Alarm Only
ON
U>Alarm U>>Trip
Voltage Prot.
2.0 .. 220.0 V
Voltage Prot.
0.00 .. 100.00 sec
Voltage Prot.
2.0 .. 220.0 V
Voltage Prot.
0.00 .. 100.00 sec
Voltage Prot.
0.30 .. 0.99
Voltage Prot.
OFF
Alarm Only
ON
U<Alarm U<<Trip
Voltage Prot.
1.0 .. 100.0 V
Voltage Prot.
0.00 .. 100.00 sec
Voltage Prot.
1.0 .. 100.0 V
Voltage Prot.
0.00 .. 100.00 sec
Voltage Prot.
ON
OFF
Voltage Prot.
1.01 .. 1.20
Voltage Prot.
OFF
Alarm Only
ON
U<Alarm U<<Trip
Voltage Prot.
1.0 .. 175.0 V
Voltage Prot.
0.00 .. 100.00 sec
Voltage Prot.
1.0 .. 175.0 V
Voltage Prot.
0.00 .. 100.00 sec
ON
OFF
Voltage Prot.
1.01 .. 1.20
Functions, Settings, Information
Default Setting
Comments
1.00 sec
T 3U0>> Time Delay (or T
Ux>>)
ON
3U0>(>): Stabilization
3U0-Measurement
0.95
3U0>(>) Reset ratio (or
Ux)
OFF
Operating mode U1 over-
voltage prot.
150.0 V
U1> Pickup
2.00 sec
T U1> Time Delay
175.0 V
U1>> Pickup
1.00 sec
T U1>> Time Delay
0.98
U1>(>) Reset ratio
OFF
Operating mode U2 over-
voltage prot.
30.0 V
U2> Pickup
2.00 sec
T U2> Time Delay
50.0 V
U2>> Pickup
1.00 sec
T U2>> Time Delay
0.98
U2>(>) Reset ratio
OFF
Operating mode Uph-e
undervoltage prot.
30.0 V
Uph-e< Pickup
2.00 sec
T Uph-e< Time Delay
10.0 V
Uph-e<< Pickup
1.00 sec
T Uph-e<< Time Delay
ON
Current supervision (Uph-
e)
1.05
Uph-e<(<) Reset ratio
OFF
Operating mode Uph-ph
undervoltage prot.
50.0 V
Uph-ph< Pickup
2.00 sec
T Uph-ph< Time Delay
17.0 V
Uph-ph<< Pickup
1.00 sec
T Uph-ph<< Time Delay
ON
Current supervision (Uph-
ph)
1.05
Uph-ph<(<) Reset ratio
E.2 Settings
295