Siemens SIPROTEC 4 7VK61 Manual page 305

Breaker management device
Table of Contents

Advertisement

Addr. Parameter
3721
3U0>(>) (or Ux)
3722
3U0>
3723
T 3U0>
3724
3U0>>
3725
T 3U0>>
3728A 3U0>(>) Stabil.
3729A 3U0>(>) RESET
3731
U1>(>)
3732
U1>
3733
T U1>
3734
U1>>
3735
T U1>>
3739A U1>(>) RESET
3741
U2>(>)
3742
U2>
3743
T U2>
3744
U2>>
3745
T U2>>
3749A U2>(>) RESET
3751
Uph-e<(<)
3752
Uph-e<
3753
T Uph-e<
3754
Uph-e<<
3755
T Uph-e<<
3758
CURR.SUP. Uphe<
3759A Uph-e<(<) RESET
SIPROTEC 4, 7VK61, Manual
C53000-G1176-C159-5, Edition 05.2018
Function
C
Setting Options
Voltage Prot.
OFF
Alarm Only
ON
U>Alarm U>>Trip
Voltage Prot.
1.0 .. 220.0 V
Voltage Prot.
0.00 .. 100.00 sec
Voltage Prot.
1.0 .. 220.0 V
Voltage Prot.
0.00 .. 100.00 sec
Voltage Prot.
ON
OFF
Voltage Prot.
0.30 .. 0.99
Voltage Prot.
OFF
Alarm Only
ON
U>Alarm U>>Trip
Voltage Prot.
2.0 .. 220.0 V
Voltage Prot.
0.00 .. 100.00 sec
Voltage Prot.
2.0 .. 220.0 V
Voltage Prot.
0.00 .. 100.00 sec
Voltage Prot.
0.30 .. 0.99
Voltage Prot.
OFF
Alarm Only
ON
U>Alarm U>>Trip
Voltage Prot.
2.0 .. 220.0 V
Voltage Prot.
0.00 .. 100.00 sec
Voltage Prot.
2.0 .. 220.0 V
Voltage Prot.
0.00 .. 100.00 sec
Voltage Prot.
0.30 .. 0.99
Voltage Prot.
OFF
Alarm Only
ON
U<Alarm U<<Trip
Voltage Prot.
1.0 .. 100.0 V
Voltage Prot.
0.00 .. 100.00 sec
Voltage Prot.
1.0 .. 100.0 V
Voltage Prot.
0.00 .. 100.00 sec
Voltage Prot.
ON
OFF
Voltage Prot.
1.01 .. 1.20
Functions, Settings, Information
Default Setting
Comments
OFF
Operating mode 3U0 (or
Ux) overvoltage
30.0 V
3U0>: Pickup value (or
Ux>)
2.00 sec
3U0>: Time delay (or
Ux>)
50.0 V
3U0>>: Pickup value (or
Ux>>)
1.00 sec
3U0>>: Time delay (or
Ux>>)
ON
3U0>(>): Stabilization
3U0-Measurement
0.95
3U0>(>): Resetting ratio
(or Ux)
OFF
Operating mode U1 over-
voltage prot.
150.0 V
V1>: 5A
2.00 sec
V1>: Time delay
175.0 V
V1>>: 5A
1.00 sec
V1>>: Time delay
0.98
V1>(>): Dropout to
pickup ratio
OFF
Operating mode U2 over-
voltage prot.
30.0 V
V2> 5A
2.00 sec
V2> Time delay
50.0 V
V2>>: 5A
1.00 sec
V2>>: Time delay
0.98
V2>(>): Dropout to
pickup ratio
OFF
Operating mode Ph-E
undervoltage prot.
30.0 V
Uph<: 5A
2.00 sec
Uph<: Time delay
10.0 V
Uph<<: 5A
1.00 sec
Uph<<: Time delay
ON
Uph<(<): Current criterion
1.05
Uph<(<): Dropout to
pickup ratio
E.2 Settings