Siemens SIPROTEC 4 7VK61 Manual page 307

Breaker management device
Table of Contents

Advertisement

Addr. Parameter
3921
End Flt. stage
3922
T-EndFault
3931
PoleDiscrepancy
3932
T-PoleDiscrep.
4001
FCT TripSuperv.
4002
No. of BI
4003
Alarm Delay
SIPROTEC 4, 7VK61, Manual
C53000-G1176-C159-5, Edition 05.2018
Function
C
Setting Options
Breaker Failure
ON
OFF
Breaker Failure
0.00 .. 30.00 sec
Breaker Failure
ON
OFF
Breaker Failure
0.00 .. 30.00 sec
TripCirc.Superv
ON
OFF
TripCirc.Superv
1 .. 2
TripCirc.Superv
1 .. 30 sec
Functions, Settings, Information
Default Setting
Comments
OFF
End fault protection
2.00 sec
Trip delay of end fault
protection
OFF
Pole Discrepancy supervi-
sion
2.00 sec
Trip delay with pole
discrepancy
OFF
TRIP Circuit Supervision is
2
Number of Binary Inputs
per trip circuit
2 sec
Delay Time for alarm
E.2 Settings
307