Fault Recording
Number of stored fault records
Storage time
Sampling rate at f
= 50 Hz
N
Sampling rate at f
= 60 Hz
N
Switching Statistics
Number of trip events caused by the device
Number of automatic reclosures initiated by the device
Total of interrupted currents
Maximum interrupted current
Real Time Clock and Buffer Battery
Resolution for operational messages
Resolution for fault messages
Buffer battery
IEC 61850 GOOSE (inter-device communication)
The GOOSE communication service of IEC 61850 is qualified for switchgear interlocking. The runtime of GOOSE
messages with the protection relay picked up depends on the number of connected IEC 61850 clients. For the devices
applications with protective functions have to be checked in terms of their required runtime. In each case, the manufac-
turer has to be consulted to define the requirements that ensure that the application functions safely.
SIPROTEC 4, 7VK61, Manual
C53000-G1176-C159-5, Edition 05.2018
Max. 8
Max. 5 s for each fault
Approx. 15 s in total
1 ms
0,83 ms
Separately for each breaker pole (if single-pole tripping is
possible)
Separate for 1-pole and 3-pole AR;
Separately for 1st AR cycle
and for all further cyles
Pole segregated
Pole segregated
1 ms
1 ms
Type: 3 V/1 Ah, Type CR 1/2 AA
Self-discharging time approx. 10 years