Information List - Siemens SIPROTEC 4 7VK61 Manual

Breaker management device
Table of Contents

Advertisement

Addr.
Parameter
3507
T-SYN. DURATION
3508
T SYNC-STAB
3509
SyncCB
3510
Op.mode with AR
3511
AR maxVolt.Diff
3512
AR maxFreq.Diff
3513
AR maxAngleDiff
3515A
AR SYNC-CHECK
3516
AR Usy1<Usy2>
3517
AR Usy1>Usy2<
3518
AR Usy1<Usy2<
3519
AR OVERRIDE
3530
Op.mode with MC
3531
MC maxVolt.Diff
3532
MC maxFreq.Diff
3533
MC maxAngleDiff
3535A
MC SYNCHR
3536
MC Usy1< Usy2>
3537
MC Usy1> Usy2<
3538
MC Usy1< Usy2<
3539
MC OVERRIDE
2.4.4

Information List

No.
Information
2901
>Sync. on
2902
>Sync. off
2903
>BLOCK Sync.
2905
>Sync. Start MC
2906
>Sync. Start AR
2907
>Sync. synch
SIPROTEC 4, 7VK61, Manual
C53000-G1176-C159-5, Edition 05.2018
Setting Options
0.01 .. 600.00 sec
0.00 .. 30.00 sec
(Einstellmöglichkeiten
anwendungsabhängig)
with T-CB close
w/o T-CB close
1.0 .. 60.0 V
0.03 .. 2.00 Hz
2 .. 80 °
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
with T-CB close
w/o T-CB close
1.0 .. 60.0 V
0.03 .. 2.00 Hz
2 .. 80 °
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
Type of
Comments
Informa-
tion
SP
>Switch on synchro-check function
SP
>Switch off synchro-check function
SP
>BLOCK synchro-check function
SP
>Start synchro-check for Manual Close
SP
>Start synchro-check for AR
SP
>Sync-Prog. Live bus / live line / Sync
2.4 Synchronism and voltage check (optional)
Default Setting
Comments
1.00 sec
Maximum duration of
synchronism-check
0.00 sec
Synchronous condition stability
timer
none
Synchronizable circuit breaker
w/o T-CB close
Operating mode with AR
2.0 V
Maximum voltage difference
0.10 Hz
Maximum frequency difference
10 °
Maximum angle difference
YES
AR at Usy2>, Usy1>, and Synchr.
NO
AR at Usy1< and Usy2>
NO
AR at Usy1> and Usy2<
NO
AR at Usy1< and Usy2<
NO
Override of any check before AR
w/o T-CB close
Operating mode with Man.Cl
2.0 V
Maximum voltage difference
0.10 Hz
Maximum frequency difference
10 °
Maximum angle difference
YES
Manual Close at Usy2>, Usy1>,
and Synchr
NO
Manual Close at Usy1< and Usy2>
NO
Manual Close at Usy1> and Usy2<
NO
Manual Close at Usy1< and Usy2<
NO
Override of any check before
Man.Cl
Functions
95