Monitoring The Phase Angle Of The Positive Sequence Power - Siemens SIPROTEC 4 7VK61 Manual

Breaker management device
Table of Contents

Advertisement

Functions
2.7 Monitoring Functions
[lo-ffm-mcl-20101014, 1, en_GB]
Figure 2-55
2.7.1.4

Monitoring the Phase Angle of the Positive Sequence Power

This monitoring function allows determining the direction of power flow. You can monitor the phase angle of
the complex power, and generate an indication when the power phasor is inside a settable segment.
One example of this application is the indication of capacitive reactive power. The monitoring indication can
then be used to control the overvoltage protection function. For this purpose, two angles must be set, as
shown in
Figure 2-56
If the measured phase angle φ(S
delimited by the angles φA and φB, the indication
φB can be freely set in the range between 0° and 359°. The area starts at φA and extends in a mathematically
positive sense as far as the angle φB. A hysteresis of 2° is provided to prevent erroneous indications which
might emerge at the threshold limits.
[blindleistung-ind-kap-wlk040602, 1, en_GB]
Figure 2-56
138
Effect of the measuring voltage failure
. In this example, φA = 200° and φB = 340° have been set.
) of the positive sequence power is innerhalb the area of the P-Q plane
1
Characteristic of the Positive Sequence System Phase Angle Monitoring
φ(PQ Pos. Seq.) (No. 130) is output. The angles φA and
C53000-G1176-C159-5, Edition 05.2018
SIPROTEC 4, 7VK61, Manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents