Functions
2.5 Under and over-voltage protection (optional)
Addr.
Parameter
3764
Uph-ph<<
3765
T Uphph<<
3768
CURR.SUP.Uphph<
3769A
Uphph<(<) RESET
3771
U1<(<)
3772
U1<
3773
T U1<
3774
U1<<
3775
T U1<<
3778
CURR.SUP.U1<
3779A
U1<(<) RESET
2.5.5

Information List

No.
Information
234.2100 U<, U> blk
10201
>Uph-e>(>) BLK
10202
>Uph-ph>(>) BLK
10203
>3U0>(>) BLK
10204
>U1>(>) BLK
10205
>U2>(>) BLK
10206
>Uph-e<(<) BLK
10207
>Uphph<(<) BLK
10208
>U1<(<) BLK
10215
Uph-e>(>) OFF
10216
Uph-e>(>) BLK
10217
Uph-ph>(>) OFF
10218
Uph-ph>(>) BLK
10219
3U0>(>) OFF
10220
3U0>(>) BLK
10221
U1>(>) OFF
10222
U1>(>) BLK
10223
U2>(>) OFF
10224
U2>(>) BLK
10225
Uph-e<(<) OFF
10226
Uph-e<(<) BLK
10227
Uph-ph<(<) OFF
10228
Uph-ph<(<) BLK
10229
U1<(<) OFF
10230
U1<(<) BLK
112
Setting Options
1.0 .. 175.0 V
0.00 .. 100.00 sec
ON
OFF
1.01 .. 1.20
OFF
Alarm Only
ON
U<Alarm U<<Trip
1.0 .. 100.0 V
0.00 .. 100.00 sec
1.0 .. 100.0 V
0.00 .. 100.00 sec
ON
OFF
1.01 .. 1.20
Type of
Comments
Informa-
tion
IntSP
U<, U> blocked via operation
SP
>BLOCK Uph-e>(>) Overvolt. (phase-earth)
SP
>BLOCK Uph-ph>(>) Overvolt (phase-phase)
SP
>BLOCK 3U0>(>) Overvolt. (zero sequence)
SP
>BLOCK U1>(>) Overvolt. (positive seq.)
SP
>BLOCK U2>(>) Overvolt. (negative seq.)
SP
>BLOCK Uph-e<(<) Undervolt (phase-earth)
SP
>BLOCK Uphph<(<) Undervolt (phase-phase)
SP
>BLOCK U1<(<) Undervolt (positive seq.)
OUT
Uph-e>(>) Overvolt. is switched OFF
OUT
Uph-e>(>) Overvolt. is BLOCKED
OUT
Uph-ph>(>) Overvolt. is switched OFF
OUT
Uph-ph>(>) Overvolt. is BLOCKED
OUT
3U0>(>) Overvolt. is switched OFF
OUT
3U0>(>) Overvolt. is BLOCKED
OUT
U1>(>) Overvolt. is switched OFF
OUT
U1>(>) Overvolt. is BLOCKED
OUT
U2>(>) Overvolt. is switched OFF
OUT
U2>(>) Overvolt. is BLOCKED
OUT
Uph-e<(<) Undervolt. is switched OFF
OUT
Uph-e<(<) Undervolt. is BLOCKED
OUT
Uph-ph<(<) Undervolt. is switched OFF
OUT
Uphph<(<) Undervolt. is BLOCKED
OUT
U1<(<) Undervolt. is switched OFF
OUT
U1<(<) Undervolt. is BLOCKED
Default Setting
Comments
17.0 V
Uph-ph<< Pickup
1.00 sec
T Uph-ph<< Time Delay
ON
Current supervision (Uph-ph)
1.05
Uph-ph<(<) Reset ratio
OFF
Operating mode U1 undervoltage
prot.
30.0 V
U1< Pickup
2.00 sec
T U1< Time Delay
10.0 V
U1<< Pickup
1.00 sec
T U1<< Time Delay
ON
Current supervision (U1)
1.05
U1<(<) Reset ratio
C53000-G1176-C159-5, Edition 05.2018
SIPROTEC 4, 7VK61, Manual