Siemens SIPROTEC 4 7VK61 Manual page 304

Breaker management device
Table of Contents

Advertisement

Functions, Settings, Information
E.2 Settings
Addr. Parameter
3515A AR SYNC-CHECK
3516
AR Usy1<Usy2>
3517
AR Usy1>Usy2<
3518
AR Usy1<Usy2<
3519
AR OVERRIDE
3530
Op.mode with MC
3531
MC maxVolt.Diff
3532
MC maxFreq.Diff
3533
MC maxAngleDiff
3535A MC SYNCHR
3536
MC Usy1< Usy2>
3537
MC Usy1> Usy2<
3538
MC Usy1< Usy2<
3539
MC OVERRIDE
3701
Uph-e>(>)
3702
Uph-e>
3703
T Uph-e>
3704
Uph-e>>
3705
T Uph-e>>
3709A Uph-e>(>) RESET
3711
Uph-ph>(>)
3712
Uph-ph>
3713
T Uph-ph>
3714
Uph-ph>>
3715
T Uph-ph>>
3719A Uphph>(>) RESET
304
Function
C
Setting Options
Sync. Check
YES
NO
Sync. Check
YES
NO
Sync. Check
YES
NO
Sync. Check
YES
NO
Sync. Check
YES
NO
Sync. Check
with T-CB close
w/o T-CB close
Sync. Check
1.0 .. 60.0 V
Sync. Check
0.03 .. 2.00 Hz
Sync. Check
2 .. 80 °
Sync. Check
YES
NO
Sync. Check
YES
NO
Sync. Check
YES
NO
Sync. Check
YES
NO
Sync. Check
YES
NO
Voltage Prot.
OFF
Alarm Only
ON
U>Alarm U>>Trip
Voltage Prot.
1.0 .. 170.0 V
Voltage Prot.
0.00 .. 100.00 sec
Voltage Prot.
1.0 .. 170.0 V
Voltage Prot.
0.00 .. 100.00 sec
Voltage Prot.
0.30 .. 0.99
Voltage Prot.
OFF
Alarm Only
ON
U>Alarm U>>Trip
Voltage Prot.
2.0 .. 220.0 V
Voltage Prot.
0.00 .. 100.00 sec
Voltage Prot.
2.0 .. 220.0 V
Voltage Prot.
0.00 .. 100.00 sec
Voltage Prot.
0.30 .. 0.99
Default Setting
Comments
YES
AR closing at Usy2>,
Usy1> and synchr
NO
AR: Closing at Usy1< and
Usy2>
NO
AR: Closing at Usy1> and
Usy2<
NO
AR: Closing at Usy1< and
Usy2<
NO
Override of any check
before AR
w/o T-CB close
Operating mode with
Man.Cl.
2.0 V
Maximum voltage differ-
ence
0.10 Hz
Maximum frequency
difference
10 °
Maximum angle differ-
ence
YES
HE: Closing at Usy2>,
Usy1> and synchr
NO
HE: Closing at Usy1< and
Usy2>
NO
HE:Closing at Usy1> and
Usy2<
NO
HE: Closing at Usy1< and
Usy2<
NO
Override of any check
before AR
OFF
Operating mode Ph-E
overvoltage prot.
85.0 V
Uph>: 5A
2.00 sec
Uph>: Time delay
100.0 V
Uph>>: 5A
1.00 sec
Uph>>: Time delay
0.98
Uph>(>): Dropout to
pickup ratio
OFF
Operating mode Uph-ph
overvoltage prot.
150.0 V
Uphph>: 5A
2.00 sec
Uphph>: Time delay
175.0 V
Uphph>>: 5A
1.00 sec
Uphph>>: Time delay
0.98
Uphph>(>): Dropout to
pickup ratio
SIPROTEC 4, 7VK61, Manual
C53000-G1176-C159-5, Edition 05.2018