Setting Notes; Settings; Information List - Siemens SIPROTEC 4 7VK61 Manual

Breaker management device
Table of Contents

Advertisement

The trip circuit supervision does not operate during system faults. A momentary closed tripping contact does
not lead to a fault indication. If, however, other trip relay contacts from different devices are connected in
parallel in the trip circuit, the fault indication must be delayed by Alarm Delay (see also
clearance of the failure in the trip circuit, the fault message automatically resets with the same time delay.
[logikdiagramm-auskruebrwchg-1-be-wlk-310702, 1, en_GB]
Figure 2-62
2.7.2.2

Setting Notes

General
The number of circuits to be supervised was set during the configuration in address 140 Trip Cir. Sup.
(Section
2.1.1.2 Setting
applied there.
The trip circuit supervision can be switched in address 4001 FCT TripSuperv. ON- or OFF. The number of
binary inputs that shall be used in each of the supervised circuits is set in address 4002 No. of BI. If the
routing of the required binary inputs does not comply with the selected monitoring mode, an alarm is issued
(
TripC ProgFAIL... with identification of the non-compliant circuit).
Supervision with one binary input
The alarm for supervision with two binary inputs is always delayed by approx. 1s to 2s, whereas the delay time
of the alarm for supervision with one binary input can be set in address 4003 Alarm Delay. If only the
device 7VK61 is connected to the trip circuits 1 s to 2 s are sufficient, as the trip circuit supervision does not
operate during a system fault. If, however, trip contacts from other devices are connected in parallel in the trip
circuit, the alarm must be delayed such that the longest trip command duration can be reliably bridged.
2.7.2.3

Settings

Addr.
Parameter
4001
FCT TripSuperv.
4002
No. of BI
4003
Alarm Delay
2.7.2.4

Information List

No.
Information
6854
>TripC1 TripRel
6855
>TripC1 Bkr.Rel
6856
>TripC2 TripRel
6857
>TripC2 Bkr.Rel
6858
>TripC3 TripRel
6859
>TripC3 Bkr.Rel
6861
TripC OFF
6865
FAIL: Trip cir.
6866
TripC1 ProgFAIL
SIPROTEC 4, 7VK61, Manual
C53000-G1176-C159-5, Edition 05.2018
Logic diagram for trip circuit supervision with one binary input
Notes). If the trip circuit supervision is not used at all, the setting Disabled must be
Setting Options
ON
OFF
1 .. 2
1 .. 30 sec
Type of
Informa-
tion
SP
SP
SP
SP
SP
SP
OUT
OUT
OUT
Default Setting
Comments
OFF
TRIP Circuit Supervision is
2
Number of Binary Inputs per trip
circuit
2 sec
Delay Time for alarm
Comments
>Trip circuit superv. 1: Trip Relay
>Trip circuit superv. 1: Breaker Relay
>Trip circuit superv. 2: Trip Relay
>Trip circuit superv. 2: Breaker Relay
>Trip circuit superv. 3: Trip Relay
>Trip circuit superv. 3: Breaker Relay
Trip circuit supervision OFF
Failure Trip Circuit
TripC1 blocked: Binary input is not set
Functions
2.7 Monitoring Functions
Figure
2-62). After
147