Siemens SIPROTEC 4 7VK61 Manual page 105

Breaker management device
Table of Contents

Advertisement

The phase-to-phase undervoltage protection can also be blocked via a binary input
is an automatic blocking if the measuring voltage failure was detected or voltage mcb tripping was indicated
(internal blocking of the phases affected by the voltage failure).
During single-pole dead time for automatic reclosure the stages of the undervoltage protection are automati-
cally blocked in the disconnected phase so that they do not respond to the undervoltage of the disconnected
phase provided that the voltage transformers are located on the outgoing side. Only such stages are blocked
during the single-pole dead time that can actually initiate tripping according to their setting.
This automatic blocking function requires the condition of the system to be detected without doubt. This
means that it is only active if all three current and voltage transformers are connected.
Undervoltage positive sequence system U
The device calculates the positive sequence system according to its defining equation
U
=
1
/
·(U
+ a·U
1
3
L1
where a = e
j120°
.
The resulting positive sequence voltage is fed to the two threshold stages U1< (address 3772) and U1<<
(address 3774 (see
U1<< (address 3775). these stages form a two-stage undervoltage protection for the positive sequence
system.
The current can be used as an additional criterion for the undervoltage protection of the positive sequence
system (current supervision CURR.SUP.U1<, address 3778). An undervoltage is only detected if the current
flow is detected in at least one phase together with the undervoltage criterion.
The undervoltage protection for the positive sequence system can be blocked via the binary input
BLK . The stages of the undervoltage protection are automatically blocked if voltage failure is detected ("Fuse-
Failure-Monitor", also see Section
transformer is indicated via the binary input
SIPROTEC 4, 7VK61, Manual
C53000-G1176-C159-5, Edition 05.2018
1
+ a
2
·U
)
L2
L3
Figure
2-30). Combined with the associated time delays T U1< (address 3773) and T
2.7.1 Measurement
>FAIL:Feeder VT .
2.5 Under and over-voltage protection (optional)
Supervision) or, if the trip of the mcb for the voltage
Functions
>Uphph<(<) BLK . There
>U1<(<)
105

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents